Omron CJ1W-CLK21-V1, CVM1-CLK21, CS1W-RPT01 Within 1 segment See Entire network, PCF type GI type

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 38
Image 38

Specifications and Configurations

Section 1-2

Communications Specifications when Using the CS1W-RPT01 Repeater Unit in a Wired Network

Item

Within 1 segment (See

Entire network

 

note 1.)

 

 

 

 

Transmission path form

Multi-drop

Tree type (Connection of

 

 

segments with Repeaters)

 

 

 

Baud rate and maximum trans-

2 Mbps: 500 m

2 Mbps: 1.5 km

mission distance (See note 2.)

1 Mbps: 800 m

1 Mbps: 2.4 km

 

500 Kbps: 1 km

500 Kbps: 3.0 km

 

 

 

Maximum number of nodes

Total number of Control-

Controller Link Units/Sup-

 

ler Link Units + Repeater

port Boards (See note 3.):

 

Units: 32 nodes (See

62 nodes

 

note 5.)

 

 

 

 

Maximum number of Repeater

---

2 stages

stages (See note 4.)

 

 

Note 1. Specifications within a segment are identical to the specifications of a Wired Controller Link Network.

2.Maximum transmission distance: Total length of cables in the longest path connecting any two nodes.

3.A maximum of 62 nodes is possible only when using CS1W-CLK21-V1, CJ1W-CLK21-V1 and 3G8F7-CLK21-V1 Units.

4.Maximum number of Repeater stages: The maximum number of Repeater Units that can be inserted into the path connecting any two nodes. For wire-to-optical connection, two Repeater Units make up a single set, which is counted as a single Repeater stage.

5.The Repeater Units each have a unique node address. Up to 32 Units, consisting of Controller Link Units and Repeater Units, can be connected within a single segment.

Wire

Optical fiber cable

:Controller Link Unit/Support Board

:Wire-to-wire Repeater Unit

:Wire-to-optical Repeater Unit (two Units used in a pair)

: Range of a single segment

Note: The Repeater Unit will be counted in the number of nodes for each segment that it is connected to.

Specifications of Optical Fiber Cables Used with Wire-to-Optical Connections

Item

H-PCF type

GI type

 

 

 

Optical fiber cable

H-PCF 200/230 m two-

GI 50/125 m two-core cable

 

core cable

or GI 62.5/125 m two-core

 

 

cable

 

 

 

Maximum transmission

Adhesion-polished: 1 km

50/125 m: 1 km

distance (See note 2.)

Crimp cut: 800 m

62.5/125 m: 2 km

 

 

 

15

Page 38
Image 38
Omron CJ1W-CLK21-V1, CVM1-CLK21, CS1W-RPT01, C200HW-CLK21, CQM1H-CLK21 Within 1 segment See Entire network, PCF type GI type