Using the Message Service

Section 6-3

C200HX/HG/HE PLCs

Execution condition

00000 25204 31002

31001

31000

S

KEEP(11)

31000

R

The transmission program will run when IR 00000 turns ON, provided that the Network Instruction En- abled Flag is ON and the RECV instruction has not been executed.

IR 31000 remains ON while the SEND instruction is being executed, and it turns OFF when instruction

31000 25204

Network Instruction Error Flag

31000 25203

(Continued on the next page)

@MOV(21)

#000A

DM 0000

@MOV(21)

#9500

DM 0001

@MOV(21)

#0003

DM 0002

@MOV(21)

#0500

DM 0020

@MOV(21)

#4000

DM 0021

@XFER(70)

#0010

000

DM 0010

@SEND(90)

DM 0010

DM 0020

DM 0000

DIFU(13) 31001

00200

execution has been completed.

Control Data Preparation

 

 

 

 

 

DM 0000

0 0

0 A

10 send words*

DM 0001

9 5

0 0

Operating level 1**

DM 0002

0 0

0 3

Node 3, Unit 0 (a PLC)

*No destination network address specified

**Response required, 5 retries, direct designa- tion, monitoring time: default

Beginning Word for Indirect Receiving by

Destination Node

DM 0020

0 5

0 0

Beginning word for

 

 

 

receiving (by destina-

DM 0021

4 0

0 0

tion node) = DM4000

 

 

 

 

 

 

(05: DM designation)

Transfers the 10 words beginning at IR 000 to the 10 words beginning at DM 0010.

Transfers the 10 words beginning at DM 0010 of the source node to the words beginning with DM 4000 (specified by DM 0020 and DM0021) at node address 3.

Creates reset input.

Turns ON to indicate transmission error.