Status Area and Troubleshooting

 

Section 9-2

Bit Status and Error Processing

 

 

Data Link Status

 

 

 

 

 

 

 

Bit status

Probable cause

Probable remedy

 

 

 

 

 

PLC’s CPU Unit error is 1:

A fatal PLC error, non-fatal

Refer to the PLC’s opera-

 

ON

PLC error, or a watchdog

tion manual and correct

 

 

timer error has occurred.

the error. If the error occurs

 

 

 

again, replace the PLC.

 

 

 

 

 

 

The Unit is mounted to a

Refer to 1-2-4 Controller

 

 

non-compatible PLC.

Link Unit Models and PLCs

 

 

 

and mount onto the correct

 

 

 

PLC.

 

 

 

 

 

Communications error is 1:

The relevant node is not in

Enter the node in the Net-

 

ON

the Network.

work.

 

 

 

 

 

 

A communications error

Conduct an echoback test

 

 

has occurred as a result of

using the Controller Link

 

 

noise.

Support Software and if

 

 

 

this does not correct the

 

 

 

error, check the usage

 

 

 

environment.

 

 

 

 

 

 

A communications error

Refer to page 287 Trouble-

 

 

has occurred.

shooting with RUN, ERC,

 

 

 

ERH and INS Indicators

 

 

 

and troubleshoot accord-

 

 

 

ingly.

 

 

 

 

 

Data link participation is 0:

The relevant node is not

Enter the relevant node in

 

OFF

part of data links.

data links. If an error

 

 

 

occurs, refer to page 291

 

 

 

Node Cannot Participate in

 

 

 

Data Link and troubleshoot

 

 

 

accordingly.

 

 

 

 

 

 

There are no active data

Activate the data links.

 

 

links in the Network.

 

 

 

 

 

 

Offset error is 1: ON

The offset is greater than

Check the number of send

 

 

the number of send words

words at the relevant node,

 

 

at the relevant node.

the number of receive

 

 

 

words at the local node

 

 

 

and the offset, then reset

 

 

 

the data link table correctly.

310

Page 333