Specifications and Configurations

 

 

Section 1-2

CS/CJ-series Controller Link Unit Models

 

 

 

 

 

 

Item

Unit Ver. 1.2 (-V1

Pre-Ver. 1.2 (-V1

Without -V1 suffix

 

suffix)

suffix)

 

 

 

 

 

Model

CS1W-CLK21-V1

CS1W-CLK21-V1

CS1W-CLK21

 

CJ1W-CLK21-V1

CJ1W-CLK21-V1

CJ1W-CLK21

 

 

 

 

Maximum number of send/receive data link

20,000 words max.

12,000 words max.

 

words (data link area for sending/receiving that

 

 

 

is created for a single node in a single CPU Unit)

 

 

 

 

 

 

Data Link Area

Area 1 and Area 2 can

Area 1 and Area 2 cannot be allocated in the

 

be allocated in the

same area.

 

 

same area.

 

 

 

 

 

 

Maximum number of Units connected to a single

8 Units

4 Units

 

CPU Unit

 

 

 

 

 

 

 

Automatic data link setting

Select from equality layout, 1:N allocations

Equality layout only

 

(common type, 1:1 type, chain type)

 

 

 

 

Changing data link allocations during active data

Supported. (Data link tables can be changed

Not supported.

links

during active data links.)

 

 

 

 

Maximum number of nodes that can be con-

62 Units (requires CS1W-RPT01 Repeater

32 Units

nected

Unit).

 

 

 

 

 

 

Mixed use

Supported (See note.)

 

 

 

 

 

 

Note A network can contain both nodes with maximum of 20,000 data link words and nodes with 12,000 data link words. When models with -V1 suffix and those without -V1 suffix are both used in the same network, 1:N automatic data links and configurations of 62 nodes cannot be used.

Use the CX-Net in CX-Programmer version 5.0 or higher to set a data link area in which the number of send and receive words exceeds 12,000 words. CX-Programmer version 3.2 or higher can be used to change data link alloca- tions while manually set data links are active.

Up to eight CS/CJ-series Controller Link Units with unit version 1.2 or later can be connected to a single CPU Unit. When connecting multiple Controller Link Units to the CPU Unit, consider the current consumption of the CPU Unit

and each CPU Bus Unit before selecting the Power Supply Unit. For details on Controller Link Unit current consumption, refer to Controller Link Unit Models

and PLCs on page 16. For details on current consumption of each Unit, refer to the operation manual of the PLC that is being used.

The following table provides an example of current consumption.

Example: Using the C200HW-PA204 Power Supply Unit supplying a maxi- mum current of 4.6 A (5 V) and maximum power of 30 W.

Name

Model

Current consumption

Number of

Current consumption

 

 

per Unit (A)

Units

 

(A)

 

 

 

 

 

 

CPU Backplane (8 slots)

CS1W-BC083

0.11 A

1

0.11

A

 

 

 

 

 

CPU Unit

CS1H-CPU67H

0.82 A

1

0.82 A

 

 

 

 

 

 

Controller Link Unit (Optical)

CS1W-CLK21-V1

0.33 A

8

2.64

A

 

 

 

 

 

 

Total

 

 

 

3.57

(power consump-

 

 

 

 

tion: 17.85 W)

 

 

 

 

 

 