Setting Data Links

Section 5-2

Note a) The total number of words in data link send and receive areas must not exceed 20,000 per node when using Controller Link Units with unit Ver. 1.2 or later, or 12,000 words per node if using pre-Ver. 1.2 Controller Link Units.

b)The following values must be satisfied for each node for the data link area 1 and area 2 so that the final word in the data link does not go beyond the last word in the PLC memory area.

(Data link start word – 1) + (Total number of send/receive words in area 1 or area 2)

6143 (CIO Area)

199 (LR Area)

32767 (DM Area, EM Area)

c)Refer to the Controller Link Support Boards Operation Manual (W307) for information on the Controller Link Support Board.

d)If CX-Net detects an error during the data link table check, trou- bleshoot the error referring to 9-4 Troubleshooting Error Mes- sages in CX-Net Data Link Table Check.

C200HX/HG/HE PLCs

Setting item

 

Setting range

PLC model

Set the model of the PLC’s CPU Unit.

 

 

 

Nodes

1 to 32

 

 

 

Set the address of the refresh nodes.

 

 

It cannot be set to a parameter exceeding the “maximum node

 

 

address” of the network parameter.

 

 

First data link sta-

Set the first word to store data link status. An area of 16 words

tus word

is used.

 

 

 

IR Area:

IR 001 to IR 220, IR 300 to IR 496 (*)

 

 

LR Area: LR 00 to LR 48

 

 

DM Area: DM 0000 to DM 5984

 

 

EM Area:

Banks 00 to 15, EM 0000 to EM 6128

 

 

 

(EM must be installed)

 

 

*: When IR 000 is specified or when the default setting (––––)

 

 

is left unchanged, the default first status word will be used.

 

 

Refer to 5-4 Checking Data Link Status for details.

 

 

 

Area 1

Data link

IR Area:

IR 000 to IR 235, IR 300 to IR 511

 

start word

LR Area: LR 00 to LR 63

 

 

 

 

DM Area: DM 0000 to DM 5999

 

 

EM Area:

Banks 00 to 15, EM 0000 to EM 6143

 

 

 

(EM must be installed)

 

 

The same area cannot be set for both area 1 and area 2. Set

 

 

different areas.

 

 

 

 

Number of

Remote nodes: 0 to the number of source words

 

words

 

Set the number of words to be received.

 

 

Local node:

0 to 1,000

 

 

 

Set the number of words to be transmitted.

 

 

The total number of words in area 1 and area 2 in each node

 

 

must not exceed 1,000.

 

 

The numbers of words in both area 1 and area 2 in each node

 

 

must not be set to 0.

 

 

 

 

Offset

Remote nodes: 0 to one less than number of source words

 

 

 

Set the offset for the data to be received.

 

 

Local node:

Cannot be set.

 

 

This setting is not required if an offset is not used.

 

 

 

 

117