Constructing Networks with Repeater Units

 

Section 3-4

Partial Conversion to Optical Fiber

 

 

Terminating

Terminating

Terminating

Resistance: ON

Resistance: ON

Resistance: ON

(Optical fiber cable)

Segment 1

Terminating

Resistance: ON

Segment 2

Repeater Unit CS1W-RPT02 or CS1W-RPT03

Combining T-Branch Wiring (2-stage Repeater) and Partial Optical Fiber

Segment 1

Terminating resistance: ON

Terminating resistance: ON

Terminating resistance: ON

Terminating resistance: ON

CS1W-RPT01

Repeater Unit

CS1W-RPT02 or

CS1W-RPT03

Repeater Unit

Segment 3

Terminating resistance: ON

Terminating resistance: ON

 

 

Segment 4

Segment 2

Terminating

Terminating

 

resistance: ON

resistance: ON

Note When constructing a network using Repeater Units, each segment must sat- isfy all of the following requirements:

The total number of Controller Link Units, Support Boards, and Repeater Units within a single segment must not exceed 32.

The total cable length of a single segment must not exceed the specified value. (500 m at 2 Mbps; 800 m at 1 Mbps; and 1 km at 500 Kbps.)

The maximum number of repeater stages that can be inserted into the path connecting any two nodes is two.

The node at each end of a segment (including Repeater Units) must have terminating resistance turned ON.

The baud rates within each segment must be set to the same value.

83

Page 106
Image 106