Omron C200HW-CLK21, CVM1-CLK21, CS1W-RPT01, CJ1W-CLK21-V1, CQM1H-CLK21, CS1W-CLK21-V1 118

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 141
Image 141

Setting Data Links

 

Section 5-2

 

 

 

 

 

 

 

Setting item

 

Setting range

 

 

 

 

 

 

 

Area 2

Data link

IR Area:

IR 000 to IR 235, IR 300 to IR 511

 

 

 

start word

LR Area: LR 00 to LR 63

 

 

 

 

 

 

 

 

DM Area: DM 0000 to DM 5999

 

 

 

 

EM Area: Banks 00 to 15, EM 0000 to EM 6143

 

 

 

 

 

(EM must be installed)

 

 

 

 

The same area cannot be set for both area 1 and area 2. Set

 

 

 

 

different areas.

 

 

 

 

 

 

 

 

Number of

Remote nodes: 0 to the number of source words

 

 

 

words

 

Set the number of words to be received.

 

 

 

 

Local node:

0 to 1,000

 

 

 

 

Set the number of words to be transmitted.

 

 

 

 

The total number of words in area 1 and area 2 in each node

 

 

 

 

must not exceed 1,000.

 

 

 

 

The numbers of words in both area 1 and area 2 in each node

 

 

 

 

must not be set to 0.

 

 

 

 

 

 

 

 

Offset

Remote nodes: 0 to one less than number of source words

 

 

 

 

 

Set the offset for the data to be received.

 

 

 

 

Local node:

Cannot be set.

 

 

 

 

This setting is not required if an offset is not used.

 

 

 

 

 

 

 

Note a) The total number of words in data link send and receive areas must not exceed 8,000 per node.

b)The following values must be satisfied for each node for the data link area 1 and area 2 so that the final word in the data link does not go beyond the last word in the PLC memory area.

(Data link start word – 1) + Total number of send/receive words in area 235 (First word IR 000 to IR 235)

511 (First word IR 300 to IR 511)

63 (LR Area)

5999 (DM Area)

6143 (EM Area)

c)Refer to the Controller Link Support Boards Operation Manual (W307) for information on the Controller Link Support Board.

d)If CX-Net detects an error during the data link table check, trou- bleshoot the error referring to 9-4 Troubleshooting Error Mes- sages in CX-Net Data Link Table Check.