7-2 Remote Programming and Monitoring

A remote PLC can be programmed and monitored across a network from a

Programming Device connected to a PLC.

7-2-1 Local Networks

SYSMAC Support Software and CV Support Software

SYSMAC Support Software

A Programming Device connected to a C200HX/HG/HE, CVM1, or CV-series CPU Unit can program and monitor a C200HX/HG/HE, CVM1, or CV-series PLC on the same network. Programming and monitoring are possible, how- ever, only for the same type of CPU Unit as the one to which the Programming Device is connected. For example, if the Programming Device is connected to a CVM1 or CV-series PLC, you can only program and monitor CVM1 or CV- series PLCs on the network.

Programming Device

Controller Link Network

Programming and monitoring

 

C200HX/HG/HE

C200HX/HG/HE

SYSMAC Support

Programming Device

 

Software (CVM1 only)

 

or

Controller Link Network

 

CV Support Software

Programming and monitoring

CVM1, or CV-series PLC

CVM1, or CV-series PLC

Note A factory automation node computer cannot remotely program or monitor. The node can only monitor Controller Link Network status.