Omron CJ1W-CLK21-V1, CVM1-CLK21, CS1W-RPT01, C200HW-CLK21, CQM1H-CLK21 Set the data link mode

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 56
Image 56

Data Links Procedures

 

Section 2-1

6. Set the data link mode.

 

 

 

 

 

 

 

 

Contents

Method

Nodes

Page

 

 

 

 

 

 

Enable 62 nodes for a

Use Support Software

All nodes

78

 

wired network.

for the PLC or the Pro-

Note: This setting

 

 

 

gramming Console.

must be made to con-

 

 

 

 

 

 

 

 

struct a network that

 

 

 

 

uses a node address

 

 

 

 

higher than 32 (See

 

 

 

 

note a.)

 

 

 

 

 

 

 

Set data link mode to

Use Support Software

Data link startup node

113

 

manual.

for the PLC or the Pro-

only

 

 

 

gramming Console.

The node that is used

 

 

 

(See note b.)

 

 

 

to start the data links

 

 

 

 

 

 

 

 

is called the startup

 

 

 

 

node. It is necessary

 

 

 

 

to decide beforehand

 

 

 

 

which node will be the

 

 

 

 

startup node.

 

 

 

 

 

 

 

Set the data link status

Use Support Software

Data link startup node

160

 

storage format. (CS/

for the PLC or the Pro-

only (See note c.)

 

 

CJ Series only)

gramming Console.

 

 

 

 

 

 

 

Note a) When using fewer than 33 nodes, make sure that the Wired Net- work 62 Node Enable Bit if the DM Parameter Area software switch is turned OFF to restrict the network to 32 nodes maximum. To construct a network that uses a node address higher than 32, all nodes must use the CS1W-CLK21-V1 or CJ1W-CLK21-V1.

b)Only node addresses 1 through 32 can be used on networks for which 62 nodes have not been enabled.

c)Be sure that the data link mode in the data link parameters in the DM Area is set to 00 when using manually set data links.

d)When using the 8-bit storage format, make sure that the relevant locations in the DM Parameter Area are set to 0. The storage for- mat used by all models other than CS1W-CLK21-V1, CS1W- CLK21, CJ1W-CLK21-V1, and CJ1W-CLK21 is fixed at 8-bit, re- gardless of the setting.

7.Register the data link tables by making the following settings for each node.

 

Contents

Method

Nodes

Page

 

 

 

 

First data link status word

Use the Controller

All nodes within the

115

 

 

Link Support Soft-

network

 

Data link nodes

 

ware or CX-Pro-

Delete from the data

 

 

 

 

Area

First data link sta-

 

grammer.

 

link tables all nodes

 

1

tus words

 

 

 

 

that are not in a data

 

 

Numbers of data

 

 

 

 

link.

 

 

link words

 

 

 

 

Data link offsets

 

 

 

 

 

 

 

 

Area

First data link sta-

 

 

 

2

tus words

 

 

 

 

 

 

 

 

 

Numbers of data

 

 

 

 

link words

 

 

 

 

 

 

 

 

 

Data link offsets

 

 

 

 

 

 

 

 

Note Offsets are used to control where data is placed within the receive area.