Troubleshooting Using Indicators

 

Section 9-1

 

Configuring a Network with 32 Nodes or Less

 

 

 

 

 

Problem

Status

Cause and Remedy

 

 

 

 

 

The node is not

The node with the

Reset the node address between 1 and

 

present in the net-

ERC indicator ON is

32, then turn the power OFF and ON

 

work.

set to a node

again.

 

(ERC indicator: ON

address of 33 or

 

 

RUN indicator: OFF

higher.

 

 

INS indicator: OFF)

 

 

 

 

 

 

 

The maximum num-

A CS1W-CLK21-V1

The Wired Network 62 Node Enable Bit

 

ber of nodes in the

or CJ1W-CLK21-V1

in the DM Parameters Area of the

 

network is set to 62.

is present in the net-

CS1W-CLK21-V1 or CJ1W-CLK-V1 is

 

 

work.

ON. Turn OFF the Wired Network 62

 

 

 

Node Enable Bit, then turn the power

 

The data link status

The corresponding

 

supply OFF and ON again.

 

is showing statuses

node is a CS1W-

 

 

 

for 62 nodes.

CLK21-V1 or CJ1W-

 

 

 

CLK21-V1.

 

 

The network partici-

 

 

 

 

 

pation status is

 

 

 

showing statuses for

 

 

 

62 nodes.

 

 

 

 

 

 

9-1-2 C200HX/HG/HE and CQM1H-series Controller Link Units

 

C200HX/HG/HE Unit

CQM1H-series Unit

 

 

 

 

 

CLK21

 

 

 

RUN

TER

 

ERC

ERH

 

INS

M/A

 

SD

RD LNK

 

 

 

 

CLK21

RUN TER

ERC ERH

INSM/A

SD RD LNK

RUN:

Operating

ERC:

Communications error

INS:

Network participation

LNK:

Data link

M/A:

Data link mode

TER:

Terminating resistance set

Troubleshooting with RUN, ERC, ERH and INS Indicators

The RUN, ERC, ERH, and INS indicators can be used to check whether Con- troller Link Unit startup and Network participation are operating normally.

Note Be sure to turn off the power to the PLC before performing any of the follow- ing.

Disconnecting the Unit or connectors.

Securing Units or connectors.

Setting hardware switches.

 

Indicators

 

Probable cause

Probable remedy

 

 

 

 

 

 

RUN

ERC

ERH

INS

 

 

 

 

 

 

 

 

Lit

Not lit

Not lit

Lit

Unit operating normally;

---

 

 

 

 

Network participation nor-

 

 

 

 

 

mal.

 

 

 

 

 

 

 

Not lit

Lit

---

---

Controller Link Unit faulty.

If the ERC indicators still

 

 

 

 

 

lights when the Unit is

 

 

 

 

 

mounted on another PLC,

 

 

 

 

 

replace the Controller Link

 

 

 

 

 

Unit.

 

 

 

 

 

 