Setting Data Links

Section 5-2

 

 

 

 

Item

Setting range

 

 

 

 

Send size (number of

Set the number of words in BCD between 0 and 1,000.

 

words) for master node

The total number of send words for master node of area 1

 

for area 1

 

and area 2 must not exceed 1,000.

 

 

 

 

Set to 0 when area 1 is not to be used or when the master

 

 

node will transmit no data.

 

 

 

 

Send size (number of

Set the number of words in BCD between 0 and 1,000.

 

words) for slave nodes for

The total number of send words per slave node of area 1

 

area 1

and area 2 must not exceed 1,000.

 

 

 

 

Set to 0 when area 1 is not to be used or when the slave

 

 

node will transmit no data.

 

 

 

 

Start word for area 2

Set the word address in BCD.

 

 

CIO Area: 0000 to 6143

 

 

LR Area: LR 000 to LR 199 (CIO 1000 to CIO 1199) (See

 

 

note.)

 

 

DM Area: DM 00000 to DM 32767

 

 

EM Area: Banks 0 to 12: EM 00000 to EM 32767

 

 

Note: When a word between LR 000 and LR 199 is spec-

 

 

ified, the data link area will be allocated between words

 

 

CIO 1000 and CIO 1199 in the CIO Area.

 

 

 

 

Area for area 2

Set the area type of area 2 as a hexadecimal number.

 

 

IR Area: 80 Hex

 

 

LR Area: 86 Hex

 

 

DM Area: 82 Hex

 

 

EM Area Banks 0 to 7: 90 to 97 Hex

 

 

Banks 8 to 12: A8 to AC Hex

 

 

When area 2 is not used: 00 Hex

 

 

 

 

Send size (number of

Set the number of words in BCD between 0 and 1,000.

 

words) for master node

The total number of send words per master node of area

 

for area 2

 

1 and area 2 must not exceed 1,000.

 

 

 

 

Set to 0 when area 2 is not to be used, or when the mas-

 

 

ter node will transmit no data.

 

 

 

 

Send size (number of

Set the number of words in BCD between 0 and 1,000.

 

words) for slave nodes for

The total number of send words per slave node of area 1

 

area 2

and area 2 must not exceed 1,000.

 

 

 

 

Set to 0 when area 2 is not to be used, or when the slave

 

 

node will transmit no data.

 

 

 

 

First word to store data

Set in BCD the first word used for storing data link status.

 

link status

When automatic setup is used, status can be stored in

 

 

the IR or CIO Area only. The number of words used to

 

 

store status depends on the data link status storage for-

 

 

mat specification as below.

 

 

0 (*)

 

 

1 to 6128 (32 nodes max., 8-bit format: 16 words used)

 

 

*: When 0 is set, the status is saved in IR 1500 + unit

 

 

number x 25 (+ 7 to + 22).

 

 

 

 

Nodes to participate in

Turn ON the bits corresponding to the nodes participating

 

the data links

in the data links.

 

 

The data links will not start unless the startup node itself

 

 

is set as a participating node.

 

 

 

Note 1. Node 1 is the master node. Node 1 must be registered as a participating node.

2.The startup node (the node that sets the above DM Area parameters and starts the data links) must be set as a participating node of the data links. If not, the data links will not start.

136

Page 159
Image 159