Setting Data Links

Section 5-2

 

 

 

 

Item

Setting range

 

 

 

 

Send size (number of

Set the number of words in BCD between 0 and 1,000.

 

words) for node of area 1

The total number of send words for area 1 and area 2

 

 

must not exceed 1,000.

 

 

When area 1 is not used, set to 0.

 

 

 

 

Area 2 data link start

Set the word address in BCD.

 

word

DM Area: DM 0000 to DM 5999

 

 

 

 

EM Area: Banks 00 to 15, EM 0000 to EM 6143

 

 

 

 

Area 2 type

Set the area type for area 2 in BCD.

 

 

DM Area: 82

 

 

EM Area: Banks 00 to 07: 90 to 97

 

 

Banks 08 to 15: A8 to AF

 

 

Area 2 not used: 00

 

 

 

 

Send size (number of

Set the number of words in BCD between 0 and 1,000.

 

words) for node of area 2

The total number of send words of area 1 and area 2

 

 

must not exceed 1,000.

 

 

When area 2 is not used, set to 0.

 

 

 

 

First data link status word

Set in BCD the first word used for storing data link status.

 

 

An area of 16 words is used for storing status.

 

 

0 (*), IR 001 to IR 220, IR 300 to IR 496

 

 

Status is stored in the IR or CIO Area only.

 

 

*: When 0 is set, status of nodes 1 to 6 is stored in

 

 

CIO 239 to CIO 241 for level 0 and in CIO 243 to CIO

 

 

245 for level 1.

 

 

 

 

Nodes to participate in

Set to ON (1) the bits corresponding to the nodes partici-

 

the data links

pating in the data links.

 

 

The data link will not start unless the startup node itself is

 

 

set as a participating node.

 

 

The data link will not start if the node is set to a parameter

 

 

exceeding the “maximum node address” of the network

 

 

parameter.

 

 

 

Note a) The total number of words in data link send and receive areas must not exceed 8,000 per node.

b)The following values must be satisfied for each node for the data link area 1 and area 2 so that the final word in the data link does not go beyond the last word in the PLC memory area.

(Data link start word – 1) + Total number of send/receive words in area 235 (First word IR 000 to IR 235)

511 (First word IR 300 to IR 511)

63 (LR Area)

5999 (DM Area)

6143 (EM Area)

c)When using area 1 only, set the data link start word, type, and the number of send words of area 2 to 0.

d)When using area 2 only, set the data link start word, type, and the number of send words of area 1 to 0.

e)The startup node must be set as a participating node of the data links. If not, the data links will not start.

146