Unit Installation

Section 3-2

Screw-mounting a Repeater Unit

Use M4 15 screws to mount the Unit as shown in the following diagram.

Two, M4

81 mm

21 mm

8 mm

Mounting a Repeater Unit on DIN Track

1,2,3... 1. Unlock the DIN Track mounting pins located on the rear of the Repeater Unit.

2.Attach the Repeater Unit by hooking it onto the DIN Track from above (1) and then pressing it into place (2).

3.Lock all DIN Track mounting pins.

DIN Track mounting pin

4.Secure the Repeater Unit by mounting one End Plate on each side of the Unit. End Plates are attached by hooking first the bottom (1) then the top of the Plate onto the DIN Track and pulling down (2). Use the screw on the each End Plate to fasten it in place.

DIN Track

Mount the Repeater Unit to DIN Track. Use at least three screws to attach the

DIN Track to the control panel.

DIN Track: PFP-50N (50 cm), PFP-100N (100 cm), PFP-100N2 (100 cm)

The DIN Track should be attached within the control panel using M4 screws spaced not more than 210 mm (not more than 6 holes) apart. Attach a DIN Track in at least 3 points for the longest DIN Track length. Tightening torque should be 1.2 N·m.

65

Page 88
Image 88
Omron CQM1H-CLK21, CVM1-CLK21, CS1W-RPT01 Screw-mounting a Repeater Unit, Mounting a Repeater Unit on DIN Track