Message Service Procedure

Section 2-2

C200HX/HG/HE: AR 0700 (operating level #0),

AR 0704 (operating level #1)

CVM1/CV Series: Word 0 of DM 2000 + 100 N

CQM1H Series: AR 0700

Note The data links will not start if there is an error in the data link tables in the startup node. Data links can be started and stopped using the Controller Link Support Software.

2-2 Message Service Procedure

The following steps outline the basic procedure for using the message ser- vice.

1,2,3...

1. Install and wire the Units.

 

 

 

 

 

 

 

 

 

 

 

Contents

 

Remarks

Page

 

 

 

 

 

 

 

 

a. Mount the Units to the PLCs.

---

 

59

 

 

 

 

 

 

 

 

b. Wire the Network.

---

 

66

 

 

 

 

 

 

2. Prepare for communications.

 

Contents

Remarks

Page

 

 

 

 

a.

Set the unit number.

CS/CJ-series, CVM1, and CV-

98

 

 

series PLCs only

 

 

 

 

b. Set the node address.

---

94, 98

 

 

 

c. Set the baud rate.

---

95, 99

 

 

 

d. Set the operating level.

C200HX/HG/HE PLCs only

95

 

 

 

 

e.

Set the terminal resistance.

---

96, 99

 

 

 

 

3.

Turn ON the power to the PLC.

 

 

 

 

 

 

 

Contents

Remarks

Page

 

 

 

 

 

Turn ON the power to the PLC.

---

---

 

 

 

 

4.

Create the I/O tables.

 

 

 

 

 

 

 

Contents

Remarks

Page

 

 

 

 

 

Create the I/O tables.

CS/CJ-series, CVM1, and CV-

---

 

 

series PLCs only

 

 

 

 

 

5. Register routing tables if using inter-network connections.

Contents

Remarks

Page

 

 

 

a. Set the local network table

---

237

 

 

 

b. Set the relay network table

---

 

 

 

 

Note Routing tables are required if any of the CVM1 and CV-series CPU Units in the Network has been manufactured on or before April 1996.

Lot No.: @ @ 4 6 . . . . . Manufactured in April 1996

Indicates the last digit of the manufacturing year. In this example, the year is 1996.

Indicates the month of manufacture. October, November, and December are indicated by x, y, and z respectively. In this example, the month is April.

40