Introduction

Section 6-1

sage service, it is advisable to prevent this situation from occurring by per- forming resend processing at the node where instructions are issued. With the SEND, RECV, and CMND instructions, resend processing is performed automatically once the number of retries has been set, so be sure to specify a number other than “0” for the number of retries.

CVM1 and CV-series PLCs CMND sends “n” bytes of command data beginning with S (the beginning word for storing command data at the source node) to node N. In return, “m” bytes of response data are stored at the source node beginning with D (the beginning word for storing response data).

 

 

 

 

 

Source node

Destination node N

15

 

0

 

 

S

 

 

 

 

 

 

 

Command

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

"n" bytes

Analysis

 

 

 

 

 

 

 

 

of com-

(S –1)

 

 

mand

 

 

 

data

 

 

n

 

 

 

 

 

 

+ 2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Response

 

D

 

 

 

 

 

 

 

 

 

 

(D –1)

 

CMND(194)

+

m

 

 

2

 

 

 

SS: Source node beginning send word

DD: Destination node beginning receive word

C: Source node first control data word

C

"m" bytes

Execution

of

 

response

 

data

 

15

0

C

"n" bytes of command data

0000 to 07C6 (Hex): 0 to 1,990 words

15

0

C+1

"m" bytes of response data

0000 to 07C6 (Hex): 0 to 1,990 words

 

15

11

8 7

0

C+2

0

 

0

 

C+4

15

11

8 7

3

0

 

0

 

 

 

0

 

 

Destination network address 00 (Hex): Local network

01 to 7F (Hex): 1 to 127

15

8 7

0

C+3

Destination unit address

00 (Hex): PLC's CPU Unit15

01 to 0F (Hex): Computer (user program)

 

(02 to 0F (Hex) are used C+5

 

when using Controller Link

 

Support Boards for PCI

 

Bus only.)

10 to 1F (Hex): Unit nos. 0 to 15

FE (Hex):

Unit connected to network

Destination node N

00 to 20 (Hex): 0 to 32 (or 00 to 3E (Hex): 0 to 62)

The same data can be broadcast to all nodes

on the network by setting the destination node address to FF (Hex).

The range of node addresses will vary for networks other than Controller Link Networks.

Number of retries

0 to F (Hex): 0 to 15 retries Communications port number: 0 to 7 (Hex)

0:Response required

1:Response not required

10 8 7 3 0

Response monitor time 0000 (Hex): 2 s

0001 to FFFF (Hex): 0.1 to 6,553.5 s

(Unit: 0.1 s)

If the baud rate is slow, then setting a small value may generate an error. The standard is approximately 4 seconds at 1 Mbps or 8 seconds at 500 kbps.

Note 1. When using CVM1 and CV-series PLCs manufactured prior to April 1996, the local network address cannot be set to “00.” Set a number other than

180

Page 203
Image 203
Omron CS1W-CLK21-V1, CVM1-CLK21, CS1W-RPT01, CJ1W-CLK21-V1, C200HW-CLK21, CQM1H-CLK21 operation manual 180