Selecting Communications InstructionsSection 6-2

6-2-2

Message Service Specifications

 

 

 

 

 

 

 

 

Item

 

Specifications

 

 

 

 

 

 

Transmission format

C200HX/HG/HE PLCs

 

 

 

1:1 SEND or RECV

 

 

 

1:N SEND (broadcast)

 

 

 

CS/CJ-series, CVM1,CV-series, or CQM1H-series PLCs

 

 

 

1:1 SEND, RECV, or CMND

 

 

 

1:N SEND or CMND; (broadcast)

 

 

 

 

 

 

Packet length

SEND: 990 words (1,980 bytes) max.

 

 

 

RECV: 990 words (1,980 bytes) max.

 

 

 

CMND: 1,990 bytes max.

 

 

 

 

 

 

Data content

SEND: Command and response for a request to send data

 

 

 

are transferred.

 

 

 

 

RECV: Command and response for a request to receive

 

 

 

data are transferred.

 

 

 

CMND: A wide range of command/response data can be

 

 

 

sent.

 

 

 

 

 

 

 

Number of simulta-

C200HX/HG/HE PLCs:

 

 

neous commands

One at a time for each of 2 operating level.

 

 

 

CS/CJ-series, CVM1, and CV-series PLCs:

 

 

 

One for each of eight ports (ports 0 to 7).

 

 

 

CQM1H-series

 

 

 

 

One

 

 

 

 

 

 

 

Response monitor time

C200HX/HG/HE or CQM1H-series PLCs

 

 

 

00:

Default setting

 

 

 

 

2 seconds (2 Mbps)

 

 

 

 

4 seconds (1 Mbps)

 

 

 

 

8 seconds (500 Kbps)

 

 

 

FF:

No monitoring

 

 

 

01 to FE:

User settings (in increments of 100 ms,

 

 

 

 

100 to 25,400 ms)

 

 

 

CS/CJ-series, CVM1, and CV-series PLCs

 

 

 

0000:

Default setting (2 s)

 

 

 

0001 to FFFF:

User settings (in increments of 0.1 s,

 

 

 

 

0.1 to 6553.5 s)

 

 

 

 

 

 

 

Number of retries

0 to F: 0 to 15

 

 

 

 

 

 

188

Page 211
Image 211