Omron CJ1W-CLK21-V1 Starting and Stopping Data Links, Data Link Areas, Manually Set Data Links

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 176
Image 176

Starting and Stopping Data Links

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Section 5-3

Data Link Areas

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Node 1

Node 2

Node 3

Node 4

Area 1 CIO 100

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

1

 

 

 

1

 

 

 

1

 

CIO 130

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

2

 

 

 

3

 

 

 

4

 

CIO 150

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

CIO 170

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Area 2 D1000

D1400

D1600

D1800

11

22

1

3

1

4

Note 1. Node 1 is the master node.

2.The startup node (the node that sets the above DM parameter and starts the data link) can be set at either a master node or a slave node.

5-3 Starting and Stopping Data Links

Data link must be started after data link areas have been created. Use any of the methods described below for the startup node to start and stop data links. (The procedure for stopping data links is performed on participating nodes.) These methods are the same for both manually and automatically set data links.

Note The data link mode (manual setting or automatic setting) and data link method are determined according to the data link setting in the startup node. In the startup node, set a data link table in the case of manual setting and data link automatic setting parameters in the case of automatic setting. If the settings are incorrect, the data link will not start.

!Caution Check the following items before starting data links. If incorrect data link tables or parameters are set, injury may result due to unexpected operation of the system. Even if the correct data link tables and parameters have been set, do not start or stop data links before verifying that there will be no adverse influence on the system.

Manually Set Data Links

Check the data link tables in each node participating in the data link to see that they are correct.

Be sure that data link tables are deleted from nodes that are not participating in the data links.

Automatically Set Data Links

Be sure that the correct DM parameters have been set in the data link startup node.

153

Page 176
Image 176
Omron CJ1W-CLK21-V1, CVM1-CLK21, CS1W-RPT01 Starting and Stopping Data Links, Data Link Areas, Manually Set Data Links