Troubleshooting Error Messages in CX-Net Data Link Table Check

Section 9-4

Error Status

The status of each bit indicates that an error has occurred as given in the dia- gram below.

1: Token timeout error

1: Polling timeout error

1: Communications controller hardware error

1: Polling node was changed

1: Nodes in Network changed (added or removed)

1: Communications controller send error

1: Node address duplication error

9-3-3 Reading and Clearing Error Logs

Error logs can be read or cleared using the Controller Link Support Software, the CX-Programmer, PLC Programming Devices, or the message service. The following examples are for the Controller Link Support Software and the message service. When using a PLC Programming Device, refer to the Pro- gramming Device’s operation manual for details.

Controller Link Support Software

Read or clear the error log using the following procedure.

1,2,3...

1.

Display the Main Menu.

 

2.

Select “E: Error log.”

 

3.

Designated the node. The error log for the designated node will be dis-

 

 

played.

 

4.

Press the F7 (Clear) Key. The designated node error log will be cleared.

Message Service

Reading an Error Log

Send the ERROR LOG READ FINS command (command code 2102) to the

 

appropriate node. Refer to 6-5-11 ERROR LOG READ.

Clearing an Error Log

Send the ERROR LOG CLEAR FINS command (command code 2103) to the

 

appropriate node. Refer to 6-5-12 ERROR LOG CLEAR.

9-4 Troubleshooting Error Messages in CX-Net Data Link Table Check

This section describes the error messages displayed during data link table checks performed with CX-Net and the required troubleshooting. Perform data link table checks by selecting Validate Table from the Table Menu in the CX-Net’s Datalink Component Screen, or when transferring data link tables (by selecting Online - Transfer to PLC).

320

Page 343
Image 343