Omron CQM1H-CLK21, CVM1-CLK21, CS1W-RPT01 Set the data link mode, Create the user program

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 64
Image 64

Message Service Procedure

 

Section 2-2

6. Set the data link mode.

 

 

 

 

 

 

 

 

Contents

Method

Nodes

Page

 

 

 

 

 

 

Enable 62 nodes for a

Use Support Software

All nodes

78

 

wired network.

for the PLC or a Pro-

This setting must be

 

 

 

gramming Console.

 

 

 

made when construct-

 

 

 

 

 

 

 

 

ing a network that

 

 

 

 

uses a node address

 

 

 

 

higher than 32 (See

 

 

 

 

note.)

 

Note When using fewer than 33 nodes, make sure that the Wired Network 62 Node Enable Bit in the DM Parameter Area software switches is turned OFF to restrict the network to 32 nodes maximum. To con- struct a network containing more than 32 nodes, all nodes must use the CS1W-CLK21-V1 or CJ1W-CLK21-V1.

7. Create the user program.

Contents

Remarks

Page

 

 

 

a. Prepare the send and receive

Stored in the memory areas of the

166

data in memory.

source node

 

 

 

 

b. Prepare the control data for the

 

 

communications instruction.

 

 

 

 

 

c. Check the conditions for exe-

The standard input conditions are

189

cuting the SEND/RECV or

the Active Node Flags for the

 

CMND instruction.

source and destination nodes, and

 

 

the Port Enabled Flag.

 

d. Execute the SEND/RECV or

---

 

CMND instruction.

 

 

 

 

 

e. Execute other instructions are

The standard input condition is the

 

required for the results of the

Port Error Flags.

 

communications instruction,

C200HX/HG/HE PLCs have 1

 

(e.g., retry or error processing

communications port for each

 

if an error occurs).

operating level. When 2 or more

 

 

communications instructions are

 

 

executed at the same time, exclu-

 

 

sive control is necessary.

 

 

CS-series, CJ-series, CVM1, and

 

 

CV-series PLCs have 8 communi-

 

 

cations ports. When 9 or more

 

 

communications instructions are

 

 

executed at the same time, exclu-

 

 

sive control is necessary.

 

 

CQM1H-series PLCs have only 1

 

 

communications port. When 2 or

 

 

more communications instructions

 

 

are executed at the same time,

 

 

exclusive control is necessary.

 

41