Omron CS1W-RPT01, CVM1-CLK21, CJ1W-CLK21-V1 Communications Specifications, Items Specifications

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 37
Image 37

Specifications and ConfigurationsSection 1-2

1-2-3

Communications Specifications

Wired System

 

 

 

 

 

 

 

Items

 

Specifications

 

 

Communications method

N:N token bus

 

 

 

Code

 

Manchester code

 

 

Modulation

Baseband code

 

 

Synchronization

Flag synchronization (conforms to HDLC frames)

 

 

Transmission path form

Multi-drop bus

 

 

Baud rate and maximum

The maximum transmission distance varies with the baud rate as follows:

transmission distance

2 Mbps:

500 m

 

 

 

 

1 Mbps:

800 m

 

 

500 Kbps: 1 km

 

 

 

Media

 

Specified shielded twisted-pair cable

 

 

Number of signal lines: 2, shield line: 1

 

 

Node connection method

PLC: Connected to a terminal block

 

 

IBM PC/AT or compatible: Connected via a special connector (included)

 

 

Maximum number of nodes

32 or 62 nodes (See note 2.)

 

 

Communications functions

Data links and message service

 

 

Number of data link words

Transmission area per node: 1,000 words (2,000 bytes) max.

 

 

Data link area (send/receive words) per node

 

 

CS/CJ Series: 20,000 words max. (unit Ver. 1.2 or later)

 

 

 

12,000 words max. (pre-Ver. 1.2)

 

 

C200HX/HG/HE, CVM1/CV, CQM1H: 8,000 words max.

 

 

Personal computer: 32,000 or 62,000 words max. (See note 3.)

 

 

Number of data link words in one network (total transmission):

 

 

 

32,000 words (64,000 bytes) or 62,000 words max. (See note 3.)

 

 

Data link areas

Bit-access areas (IR, AR, LR, CIO), DM Area (DM), and extended DM Area (EM)

 

 

Message length

2,012 bytes max. (including the header)

 

 

RAS functions

Polling node backup function

 

 

Self-diagnosis function (hardware checking at startup)

 

 

Echoback test and broadcast test (using the FINS command)

 

 

Watchdog timer

 

 

Error log function

 

 

Error control

Manchester code check

 

 

CRC check (CCITT X16 + X12 + X5 + 1)

Note 1. The maximum distance between nodes depends on the connector and ca- ble processing methods.

2.At least one Repeater Unit is required to construct networks that uses a node address higher than 32. The following Controller Link Units/Support Boards must also be used, and the Wired Network 62 Node Enable Bit of the DM Parameter Area software switch of all nodes must be turned ON (62 nodes max.).

CS1W-CLK21-V1, CJ1W-CLK21-V1, and 3G8F7-CLK21-V1

3.62,000 data link words applies to configurations of 62 nodes.