Omron CJ1W-CLK21-V1, CVM1-CLK21, CS1W-RPT01, C200HW-CLK21, CQM1H-CLK21 Calculation Example

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 278
Image 278

Data Link I/O Response Time

 

Section 8-3

 

 

 

 

 

PLCs

Words per data exchange

 

 

 

 

 

 

CS/CJ-series PLCs

Approx. 7,800 words

 

 

 

 

 

 

CVM1 and CV-series PLCs

Approx. 3,700 words

 

 

 

 

 

 

C200HX/HG/HE PLCs

Approx. 4,000 words

 

 

 

 

 

 

CQM1H-series PLCs

Approx. 1,200 words

 

 

 

 

 

Note 1. Use the above equations only if only one Controller Link Unit is mounted on the PLC. If other CPU Bus Units are mounted on the PLC, obtain the refresh times for each CPU Bus Unit and add to the above equations.

2.The execution of some items takes precedence over data link area refresh- ing. For example, data link area refreshing will not take place during exe- cution of the SEND(192), RECV(193), or FAL(006) instruction.

8-3-3 Calculation Example

The data links of the Controller Link Unit require a slight time delay from the time the data link area of one node is changed until this change is reflected in the data link area at another node. This time delay is called the data link I/O response time. The following is a calculation example of the maximum and minimum I/O response times for the system configuration shown below.

PLC

Input

 

 

C

 

PLC

 

 

L

 

 

 

 

K

 

 

 

 

#1

 

 

 

 

 

 

 

Input LRXXXX

 

 

 

 

 

 

 

 

CLK: Controller Link Unit

 

 

 

 

 

 

 

 

 

 

 

C

 

 

 

 

 

 

System configuration

 

 

L

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Baud rate:

2 Mbps

 

K

 

 

 

 

 

 

 

#1

 

 

 

 

 

 

Maximum node address:

32

 

 

 

 

 

 

 

Number of polled nodes per comm cycle:

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Number of event-frames per comm cycle:

35

 

 

 

 

 

 

 

 

Nodes in network:

8 nodes

 

 

 

 

 

 

 

 

Nodes in data links:

8 nodes

 

LRXXXX

Output

Words sent in area 1:

8 words per node

 

 

Words in area 2:

16 words per node

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No messages communications are performed.

A single Controller Link Unit is mounted to each

CPU Rack.

The data link I/O response time depends on the communications cycle time, input ON delay, output ON delay, and the cycle times of the PLCs involved. The values are detailed below.

Communications Cycles

Communications cycle time =

Time

10 (8 + 16) 8 + 600 4 + 290 8 + 320 0 + 4 0 + 3,290

 

= 9,930 s 9.9 ms

Input ON Delay

The input ON delay is the time it takes for an input device to turn ON an input

 

to the PLC after receiving an input signal. In this system the input ON delay is

 

1.5 ms.

Output ON Delay

The output ON delay is the time it takes for an output device to turn ON an

 

output signal after receiving an output from the PLC. In this system the output

 

ON delay is 15 ms.

Cycle Times

The cycle time of the PLC at node #1 is 25 ms.

 

The cycle time of the PLC at node #7 is 10 ms.

255

Page 278
Image 278
Omron CJ1W-CLK21-V1, CVM1-CLK21, CS1W-RPT01, C200HW-CLK21, CQM1H-CLK21, CS1W-CLK21-V1 operation manual Calculation Example