Status Area and Troubleshooting

 

Section 9-2

Other Status

 

 

 

 

 

 

 

Bit status

Probable cause

Probable remedy

 

 

 

 

 

Duplicate Operating Lev-

The same operating level is

If two units are required,

 

els/Refresh Error:

set twice within the same

set them to different oper-

 

Operating level 0: AR0011

PLC.

ating levels.

 

 

 

 

Operating level 1: AR0010

A refresh error has

Secure the Controller Link

 

One of the above flags is 1:

occurred between the PLC

Unit firmly.

 

ON

and the Unit.

For C200HX/HG/HE PLCs,

 

 

 

tighten the screws on the

 

 

 

Bus Connection Unit.

 

 

 

If the error occurs even

 

 

 

when the Unit is mounted

 

 

 

on another PLC, replace

 

 

 

the Controller Link Unit.

 

 

 

 

 

Routing Table Error/Unit

The routing table data

Refer to 7-4 Setting Rout-

 

Restart:

within the DM Area is dam-

ing Tables and reset cor-

 

Operating level 0: AR0113

aged.

rectly. If the error occurs

 

 

again, replace the Control-

 

Operating level 1: AR0112

 

 

 

ler Link Unit.

 

One of the above flags is 1:

 

 

There is an error in the

When using routing tables

 

ON

 

 

routing table setting or a

refer to 7-4 Setting Routing

 

 

Routing Table Enable Bit

Tables and reset them cor-

 

 

(software switch) setting

rectly.

 

 

error.

When no routing tables are

 

 

 

 

 

 

being used, turn OFF the

 

 

 

Routing Table Enable Flag.

 

 

 

 

 

Communications controller

The Controller Link Unit is

Replace the Controller Link

 

hardware error:

faulty.

Unit.

 

Operating level 0: AR1114

 

 

 

Operating level 1: AR1514

 

 

 

One of the above flags is 1:

 

 

 

ON

 

 

 

 

 

 

 

EEPROM error:

An error occurred when

Remake and set the data

 

Operating level 0: AR1115

writing data to EEPROM.

link table and the network

 

 

parameters. If the error

 

Operating level 1: AR1515

The EEPROM data link

 

occurs again, replace the

 

One of the above flags is 1:

tables or the network

 

Controller Link Unit.

 

ON

parameters are damaged.

 

 

 

 

There is an error in the

 

 

 

data link or network param-

 

 

 

eter settings.

 

 

 

 

 

 

Inconsistent network

Indicates that the network

Check the network param-

 

parameters:

parameters in the

eters on the Network,

 

Operating level 0: AR2407

EEPROM of the Controller

using the Controller Link

 

Link Unit differ from those

Support Software, and

 

Operating level 1: AR2406

 

in the Network.

reset the necessary

 

One of the above flags is 1:

 

ON

 

parameters.

 

 

 

 

 

 

 