Omron CVM1-CLK21, CS1W-RPT01, CJ1W-CLK21-V1, C200HW-CLK21 C200HX/HG/HE Startup Node, Settings

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 168
Image 168

Setting Data Links

Section 5-2

11.If the LR Area in the C200HX/HG/HE or CQM1H-series PLC is automati- cally set for a data link with a CVM1, CV-series PLC or CS/CJ-series PLC, the LR words will be linked to CIO 1000 to CIO 1063 in the CVM1, CV-se- ries or CS/CJ-series PLC. CIO 1064 to CIO 1199 cannot be linked with C200HX/HG/HE or CQM1H-series PLCs in this way.

C200HX/HG/HE or CQM1H-series PLCs

LR00 to

LR63

CS/CJ-series PLCs

1000

 

 

to

 

IR words of CS/CJ-series PLCs

 

 

1063

 

= (LR words of C200HX/HG/HE or

 

CQM1H-series PLC) + 1000

1064

 

 

to

 

Cannot be directly linked

 

 

with C200HX/HG/HE words.

1199

 

 

C200HX/HG/HE Startup Node

Set the following DM Parameter Area of the PLC of the startup node.

N:Level 0 = DM 6400 Level 1 = DM 6420

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Word N

0

0

0

0

0

0

0

 

 

 

 

0

0

0

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0:

Always specify 0.

 

 

 

 

 

 

 

 

 

 

Data link mode

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– :

By other setting

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set to 01 for automatic setting.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(00 is for manual setting. Other values are invalid.)

15

8

7

 

0

 

N+1 Area 1 data link start word (BCD)

N+2 Area 1 type

00

 

 

 

N+3 Number of send words per node of area 1 (BCD)

N+4

Rightmost 4 digits of data link start word of area 2 (DM area) (BCD)

N+5

Area 2 type

Leftmost digit of data link start word of

area 2 (BCD)

N+6 Number of send words per node of area 2 (BCD)

N+7 First data link status word (BCD)

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

N+8 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1

N+9 32 31 30 29 28 27 26 25 24 23 22 21 20 19 18 17

BCD: Set the value as binary-coded decimal.

Nodes to participate in the data links

The numbers indicate node numbers. The value assigned indicates whether the node is to participate in the data links.

Participate: 1

Not participate: 0

Settings

Item

Setting range

 

 

Data link mode

Specify automatic (01).

 

 

Area 1 data link start

Set the word address in BCD.

word

IR Area: IR 000 to IR 235, IR 300 to IR 511

 

 

LR Area: LR 00 to 63

 

 

Area 1 type

Set the area for area 1 in BCD.

 

IR Area: 80

 

LR Area: 86

 

Area 1 not used: 00

 

 

145

Page 168
Image 168
Omron CVM1-CLK21, CS1W-RPT01, CJ1W-CLK21-V1, C200HW-CLK21, CQM1H-CLK21, CS1W-CLK21-V1 C200HX/HG/HE Startup Node, Settings