What Are Data Links?Section 5-1

5-1-2

Differences between Manual and Automatic Setting

 

 

 

 

 

 

 

Item

Manual setting

Automatic setting

 

 

 

 

 

 

 

Determination of

Determined by setting data link

Determined by the data link

 

 

nodes to be in a

tables.

parameters set in the data link

 

 

data link

 

startup node (the node used to

 

 

 

 

start the data links).

 

 

 

 

 

 

 

Data link settings

Set in data link tables that are

Determined by the data link

 

 

 

set in the nodes to participate in

parameters set in the data link

 

 

 

data links.

startup node (the node used to

 

 

 

 

start the data links).

 

 

 

 

 

 

 

Data link areas 1

In each node, area 1 and area

Area 1 is selected from bit-

 

 

and 2

2 are selected from bit-access

access areas (IR, CIO, and LR

 

 

 

areas (IR, CIO, and LR Areas)

Areas) and area 2 is selected

 

 

 

and DM Area (DM and EM

from DM Area (DM and EM

 

 

 

Areas).

Areas).

 

 

 

However, areas 1 and 2 cannot

 

 

 

 

be set in the same memory

 

 

 

 

area.

 

 

 

 

 

 

 

 

Refresh starting

Can be set freely in each node.

Can be set freely. (See note a))

 

 

word

(See note a))

 

 

 

 

 

 

 

 

Data link status

Selected from bit-access areas

Selected from bit-access areas

 

 

area

(IR, CIO, and LR Areas) and

(IR or CIO Areas).

 

 

 

DM Area (DM and EM Areas) in

 

 

 

 

each node.

 

 

 

 

 

 

 

 

Refresh sequence

Can be set in each node freely.

Node addresses are in ascend-

 

 

 

 

ing order.

 

 

 

 

 

 

 

Data reception

It is possible to set in each

The entire data sent from each

 

 

 

node whether the entire data or

node that is participating in the

 

 

 

a part of the data sent from

data link is received.

 

 

 

another node is received. It is

 

 

 

 

also possible to not receive the

 

 

 

 

data sent from a specific node.

 

 

 

 

(See note b))

 

 

 

 

 

 

 

 

Data transmission

The send sizes can be set

In area 1 and area 2, data send

 

 

 

freely in each node. It is also

sizes are the same in each

 

 

 

possible for certain node not to

node.

 

 

 

send data. (See note b))

 

 

 

 

 

 

Note a) The following are true for computer nodes (i.e., computers with a

Controller Link Support Board mounted).

The data link starting position is fixed.

Because areas such as bit-access areas and the DM Area are not sup- ported, areas must be made available on the computer for linking.

Automatically set data links cannot be started from the Controller Link Support Board.

The Controller Link Support Board can participate in automatically set data links.

b)If data links are manually set, send/receive area can be selected in each node, allowing send/receive groups to be created within the network in area 1 and area 2, as shown below.

Area 1

#1

 

 

#1

 

 

 

 

#2

 

#2

#1

#2

#3

 

 

#4

#3

 

#3

 

#4 #4

GroupGroup

112

Page 135
Image 135
Omron C200HW-CLK21, CVM1-CLK21 Differences between Manual and Automatic Setting, Manual setting Automatic setting