Omron CQM1H-CLK21 Configuring a Network with 33 Nodes or More, Problem Status Cause and remedy

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 304
Image 304

Troubleshooting Using Indicators

 

Section 9-1

 

Configuring a Network with 33 Nodes or More

 

 

 

 

 

Problem

Status

Cause and remedy

 

 

 

 

 

The node is not

The ERC indicator is

The Wired Network 62 Node Enable Bit

 

present in the net-

ON in the CS1W-

in the DM Parameters Area is turned

 

work.

CLK21-V1 or CJ1W-

OFF. Turn ON the Wired Network 62

 

(ERC indicator: ON

CLK21-V1, and a

Node Enable Bit and then turn the

 

RUN indicator: OFF

node address higher

power supply OFF and ON again.

 

INS indicator: OFF)

than 32 is set.

 

 

 

 

 

 

 

The ERC indicator is

The Units that can be used to configure

 

 

ON in the C200HW-

a network that uses a node address

 

 

CLK21, CQM1H-

higher than 32 are the CS1W-CLK21-

 

 

CLK21, CVM1-

V1 and CJ1W-CLK21-V1 only. Either

 

 

CLK21, CS1W-

configure the network using compatible

 

 

CLK21, or CJ1W-

Units and Boards, or split the network

 

 

CLK21, and a node

into two separate networks.

 

 

address higher than

 

 

 

32 is set.

 

 

 

 

 

 

The node is not

The INS indicator is

 

 

present in the net-

ON for some nodes

 

 

work

in the same net-

 

 

(ERC indicator: OFF

work. Those nodes

 

 

RUN indicator: ON

are C200HW-

 

 

INS indicator: OFF)

CLK21, CQM1H-

 

 

 

CLK21, CVM1-

 

 

 

CLK21, CS1W-

 

 

 

CLK21, or CJ1W-

 

 

 

CLK21.

 

 

 

 

 

 

 

The INS indicator is

The Wired Network 62 Node Enable Bit

 

 

ON for some nodes

in the DM Parameters Area of the poll-

 

 

in the same net-

ing node (CS1W-CLK21-V1 or CJ1W-

 

 

work. Those nodes

CLK-V1 with INS indicator ON) is OFF.

 

 

are CS1W-CLK21-

Turn ON the Wired Network 62 Node

 

 

V1 or CJ1W-CLK-

Enable Bit, then turn the power supply

 

 

V1.

OFF and ON again.

 

 

 

The maximum number of nodes set in

 

 

 

the network parameters is less than the

 

 

 

number of nodes present in the net-

 

 

 

work.

 

 

 

Use CX-Net or the Controller Link Sup-

 

 

 

port Software to read the network

 

 

 

parameters, and check the maximum

 

 

 

number of nodes setting. Set the maxi-

 

 

 

mum number of nodes to a number that

 

 

 

is the same or larger than the number

 

 

 

of nodes in the network.

 

 

 

 

 

The maximum num-

The polling node is a

The Units that can be used to configure

 

ber of nodes in the

C200HW-CLK21,

a network that uses a node address

 

network is set to 32.

CQM1H-CLK21,

higher than 32 are the CS1W-CLK21-

 

 

CVM1-CLK21,

V1 and CJ1W-CLK21-V1 only. Either

 

 

CS1W-CLK21, or

configure the network using compatible

 

 

CJ1W-CLK21.

Units and Boards, or split the network

 

 

 

into two separate networks.

 

 

 

 

 

 

The polling node is a

The Wired Network 62 Node Enable Bit

 

 

CS1W-CLK21-V1 or

in the DM Parameters Area of the poll-

 

 

CJ1W-CLK-V1.

ing node (CS1W-CLK21-V1 or CJ1W-

 

 

 

CLK-V1 with INS indicator ON) is OFF.

 

 

 

Turn ON the Wired Network 62 Node

 

 

 

Enable Bit, then turn the power supply

 

 

 

OFF and ON again.

281

Page 304
Image 304
Omron CQM1H-CLK21, CVM1-CLK21, CS1W-RPT01 Configuring a Network with 33 Nodes or More, Problem Status Cause and remedy