Troubleshooting Using Indicators

 

 

 

 

 

 

 

 

Section 9-1

 

 

 

 

 

 

 

 

 

 

 

 

 

Indicators

 

 

Probable cause

Probable remedy

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LNK

M/A

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Lit

---

 

Data link operating normally.

---

 

 

 

 

 

 

 

 

 

 

 

 

 

Flashing

Lit

 

When manual setting is used,

Refer to 5-2-2 Manual Setting

 

 

 

 

 

there is an error in the data link

and remake the data link table.

 

 

 

 

 

table.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flashing

Not lit

 

When automatic setting is

Refer to 5-2-4 Automatic Set-

 

 

 

 

 

used, the data link parameters

ting, reset the parameters for

 

 

 

 

 

at the startup node are incor-

the startup node DM Area so

 

 

 

 

 

rect for the local node (the

that the local node can partici-

 

 

 

 

 

data link area is out of range

pate in the data link, and then

 

 

 

 

 

for the local node.)

restart the data link.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Automatic setting is used with

Use a Controller Link Unit that

 

 

 

 

 

1:N allocations, but the device

supports automatic data link

 

 

 

 

 

does not support this function.

creation with 1:N allocations.

 

 

 

 

 

 

 

 

 

 

 

Refer to Automatic Setting on

 

 

 

 

 

 

 

 

 

 

 

page 129 for details.

 

 

 

 

 

 

 

 

 

 

 

 

 

Not lit

Lit

 

When manual setting is used,

Set data link tables for the

 

 

 

 

 

there are no data link tables

local node.

 

 

 

 

 

set for the local node.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Not lit

Not lit

 

When automatic setting is

Stop the data links, remake

 

 

 

 

 

used, the startup node is not

and set the parameters in the

 

 

 

 

 

set to participate in the data

startup node’s DM Area, and

 

 

 

 

 

links.

 

 

 

then restart the data link.

Data Link Cannot be

 

 

 

 

 

 

 

 

Stopping the data link depends on the Controller Link Unit operating normally

Stopped

 

and participating

in the Network. Read the

above explanations before

 

 

attempting to stop operation.

 

 

 

 

 

Note

Stop the data link from the node at which the LNK indicator is lit (indicating

 

 

active data links). Data links cannot be stopped from nodes which do not have

 

 

active data links.

 

 

 

 

 

 

 

 

9-1-3

CVM1 and CV-series Controller Link Units

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CLK21

 

 

 

 

 

 

 

 

 

 

 

RUN

TER

 

 

 

 

 

 

 

 

 

ERC

ERH

 

 

 

 

 

 

 

 

 

 

M/A

 

 

 

 

 

 

 

 

 

INS

LNK

 

 

 

 

 

 

 

 

 

SD

RD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RUN:

Operating

 

 

 

 

 

 

 

ERC:

Communications error

 

 

 

 

 

 

INS:

Network participation

 

 

 

 

 

 

LNK:

Data link

 

 

 

 

 

 

 

M/A:

Data link mode

 

Troubleshooting with RUN, ERC, ERH and INS Indicators

The RUN, ERC, ERH and INS indicators can be used to check whether Con- troller Link Unit startup and Network participation are operating normally.

Note Be sure to turn off the power to the PLC before performing any of the follow- ing.

Disconnecting the Unit or connectors.

Securing Units or connectors.

287

Page 310
Image 310
Omron CQM1H-CLK21, CVM1-CLK21, CS1W-RPT01, CJ1W-CLK21-V1, C200HW-CLK21 CVM1 and CV-series Controller Link Units, Stopped