Troubleshooting Using Indicators

 

 

 

Section 9-1

Node Cannot Participate

The following table describes the LNK and M/A indicators when a node can-

in Data Link

not participate in the data links.

 

 

Data link participation depends on the Controller Link Unit operating normally

 

and participating in the Network. Refer to Troubleshooting with RUN, ERC,

 

ERH and INS Indicators earlier in this section and check Unit operation before

 

using the following table.

 

 

 

 

 

 

 

 

Indicators

 

Probable cause

Probable remedy

 

 

 

 

 

 

 

LNK

M/A

 

 

 

 

 

 

 

 

 

 

Lit

---

 

Data link operating normally.

---

 

 

 

 

 

 

 

Flashing

Lit

 

When manual setting is used,

Refer to 5-2-2 Manual Setting

 

 

 

 

there is an error in the data link

and remake the data link table.

 

 

 

 

table.

 

 

 

 

 

 

 

 

Flashing

Not lit

 

When automatic setting is

Refer to 5-2-4 Automatic Set-

 

 

 

 

used, the data link parameters

ting, reset the parameters for

 

 

 

 

at the startup node are incor-

the startup node DM Area so

 

 

 

 

rect for the local node (the

that the local node can partici-

 

 

 

 

data link area is out of range

pate in the data link, and then

 

 

 

 

for the local node.)

restart the data link.

 

 

 

 

 

 

 

 

 

 

Automatic setting is used with

Use a Controller Link Unit that

 

 

 

 

1:N allocations, but the device

supports automatic data link

 

 

 

 

does not support this function.

creation with 1:N allocations.

 

 

 

 

 

Refer to Automatic Setting on

 

 

 

 

 

page 129 for details.

 

 

 

 

 

 

 

Not lit

Lit

 

When manual setting is used,

Set data link tables for the

 

 

 

 

there are no data link tables

local node.

 

 

 

 

set for the local node.

 

 

 

 

 

 

 

 

Not lit

Not lit

 

When automatic setting is

Stop the data links, remake

 

 

 

 

used, the startup node is not

and set the parameters in the

 

 

 

 

set to participate in the data

startup node’s DM Area, and

 

 

 

 

links.

then restart the data link.

Data Link Cannot be

Stopping the data link depends on the Controller Link Unit operating normally

Stopped

and participating

in the Network. Read the

above explanations before

 

attempting to stop operation.

 

Note

Stop the data link from the node at which the LNK indicator is lit (indicating

 

active data links). Data links cannot be stopped from nodes which do not have

 

active data links.

 

 

 

9-1-4 Repeater Units

PWR

T/R1

T/R2

PWR:

ON

T/R1:

SL1 com

T/R2:

SL2 com

Note Be sure to turn OFF the power to the Repeater Unit before disconnecting or reconnecting cables.