Omron CVM1-CLK21, CS1W-RPT01, CJ1W-CLK21-V1, C200HW-CLK21 Troubleshooting with Status Flags

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 324
Image 324

Status Area and Troubleshooting

Section 9-2

Data Link Status: First Data Link Status Word + 0 to + 15

Node

2

Node

1

Node

4

Node

3

Node

6

Node

5

Node

8

Node

7

Node

10

Node

9

Node

12

Node

11

Node

14

Node

13

Node

16

Node

15

Node

18

Node

17

Node

20

Node

19

Node

22

Node

21

Node

24

Node

23

Node

26

Node

25

Node

28

Node

27

Node

30

Node

29

Node

32

Node

31

PLC status

0:Inactive (user program not running)

1:Active (user program running)

PLC's CPU Unit error

0:Normal

1:Error

Communications error (data link reception)

0:Normal

1:Error

Data link participation

0:Not in data link or data link inactive

1:In data link

 

 

 

Offset error

Error: Offset exceeds

 

 

 

 

 

 

0: Normal

number of send words.

 

 

 

1: Error

 

 

Insufficient (short) receive area Insufficient: Receive

 

 

0: Sufficient

area is smaller than

 

1: Insufficient

send area. Excess data

 

 

 

 

is truncated; other data

 

 

 

 

is received.

Remaining receive area

Remaining: Receive

0: Not remaining

area is larger than send

1: Remaining

area. Data is received

 

 

 

 

and remaining words

 

 

 

 

are cleared.

Note Refer to 5-4 Checking Data Link Status for details on status flags.

Troubleshooting with Status Flags

Data Link Status

Bit status

Probable cause

Probable remedy

 

 

 

PLC’s CPU Unit error is 1:

A fatal PLC error, non-fatal

Refer to the PLC’s opera-

ON

PLC error, or a watchdog

tion manual and correct

 

timer error has occurred.

the error. If the error occurs

 

 

again, replace the PLC.

 

 

 

 

The Unit is mounted to a

Refer to 1-2-4 Controller

 

non-compatible PLC.

Link Unit Models and PLCs

 

 

and mount onto the correct

 

 

PLC.

 

 

 

Communications error is 1:

The relevant node is not in

Enter the node in the Net-

ON

the Network.

work.

 

 

 

 

A communications error

Conduct an echoback test

 

has occurred as a result of

using the Controller Link

 

noise.

Support Software and if

 

 

this does not correct the

 

 

error, check the usage

 

 

environment.

 

 

 

 

A communications error

Refer to page 276 Trouble-

 

has occurred.

shooting with RUN, ERC,

 

 

ERH and INS Indicators

 

 

and troubleshoot accord-

 

 

ingly.

 

 

 

301

Page 324
Image 324
Omron CVM1-CLK21, CS1W-RPT01 Troubleshooting with Status Flags, Data Link Status First Data Link Status Word + 0 to +