Omron CJ1W-CLK21-V1, CVM1-CLK21, CS1W-RPT01 C200HX/HG/HE Controller Link Units, C200HX/HG/HE PLC

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 116
Image 116

C200HX/HG/HE Controller Link Units

Section 4-3

Note 1. Always turn OFF the PLC’s power before setting the terminating resistance switch.

2.Turn ON the switch to connect terminating resistance at the nodes at both ends of the Network and turn OFF the switch at all other nodes. Normal communication cannot be performed in the Network unless all the nodes are set properly.

3.The TER LED indicator will light when the terminating resistance switch is set to ON.

4.The default setting is OFF (not connected).

4-3 C200HX/HG/HE Controller Link Units

The following settings are required for a Controller Link Unit used with a

C200HX/HG/HE PLC.

Item

Switch

Page

 

 

 

Node address

Node address switches

94

 

 

 

Baud rate

Baud rate and operating level switch, pins 1

95

 

and 2

 

 

 

 

Operating level

Baud rate and operating level switch, pin 4)

95

 

 

 

Terminating resistance

Terminating resistance switch

96

 

 

 

93

Page 116
Image 116
Omron CJ1W-CLK21-V1, CVM1-CLK21, CS1W-RPT01, C200HW-CLK21, CQM1H-CLK21 C200HX/HG/HE Controller Link Units, C200HX/HG/HE PLC