“00” as the local network address in the routing tables, and then specify that number.

2.With the message service, there is no guarantee that a message to a des- tination node will reach its destination. It is always possible that the mes- sage may be lost in transit due to noise or some other condition. When using the message service, it is advisable to prevent this situation from oc- curring by performing resend processing at the node where instructions are issued. With the SEND, RECV, and CMND instructions, resend pro- cessing is performed automatically once the number of retries has been set, so be sure to specify a number other than “0” for the number of retries.