Status Area and Troubleshooting

 

Section 9-2

Other Status

 

 

 

 

 

 

 

Bit status

Probable cause

Probable remedy

 

 

 

 

 

Error log exists (CIO 1500

Error information on the

Using the Controller Link

 

+ 25 n, bit 15) is 1: ON

Controller Link Unit (an

Support Software or an

 

 

error log) has been

FINS command, read the

 

 

recorded.

cause of the current error.

 

 

 

Alternatively, use past error

 

 

 

log records to troubleshoot

 

 

 

the problem.

 

 

 

 

 

Communications controller

The Controller Link Unit is

Replace the Controller Link

 

send error (CIO 1500 + 25

faulty.

Unit.

 

n, bit 11) is 1: ON

 

 

 

 

 

 

 

Inconsistent network

Indicates that the network

Check the network param-

 

parameters (CIO 1500 +

parameters recorded in the

eters on the Network in

 

25 n, bit 10) is 1: ON

CS/CJ Bus Unit Area differ

use using the Controller

 

 

from the values of the Net-

Link Support Software, and

 

 

work in use.

reset necessary parame-

 

 

 

ters.

 

 

 

 

 

Node address duplicate

The same node address

Reset so that each node

 

setting error (CIO 1500 +

has been used more than

address is used only once

 

25 n, bit 9) is 1: ON

once.

within the same Network.

 

 

 

 

 

EEPROM error (CIO 1500

An error has occurred

Check the status of bits 00

 

+ 25 n, bit 7) is 1: ON

while writing data to the

to 02 in (CIO 1500 + 25

 

 

CPU Unit’s EEPROM.

n, and correct any prob-

 

 

 

lems found. If the error

 

 

 

occurs again, replace the

 

 

 

CPU Unit.

 

 

 

 

 

PLC system setting error

The CPU Unit’s EEPROM

Check the status of bits 00

 

(CIO 1500 + 25 n, bit 3)

data is damaged.

to 02 in (CIO 1500 + 25

 

is 1: ON

 

n, and correct any prob-

 

 

 

lems found. If the error

 

 

 

occurs again, replace the

 

 

 

CPU Unit.

 

 

 

 

 

 

The PLC is protected.

Set the PLC’s protect

 

 

 

switch to OFF.

 

 

 

 

 

Routing table error

The routing table data

Refer to 7-4 Setting Rout-

 

(CIO 1500 + 25 n, bit 2)

within the CPU Unit’s

ing Tables and reset the

 

is 1: ON

EEPROM is damaged.

routing tables correctly. If

 

 

 

the error occurs again,

 

 

 

replace the Controller Link

 

 

 

Unit.

 

 

 

 

 

 

There is an error in the

When using a routing

 

 

routing table setting.

table, refer to 7-4 Setting

 

 

 

Routing Tables and reset

 

 

 

the routing tables correctly.

 

 

 

If no routing tables are

 

 

 

being used, delete the

 

 

 

tables.

 

 

 

 

297

Page 320
Image 320
Omron CJ1W-CLK21-V1, CVM1-CLK21, CS1W-RPT01, C200HW-CLK21, CQM1H-CLK21, CS1W-CLK21-V1 Other Status, Refer to 7-4 Setting Rout