Starting and Stopping Data Links

Section 5-3

5-3-1 Using a Programming Device or the User Program

Set the software switch (AR or DM Start Bit) in the PLC to ON using a Pro- gramming Device or from the user program.

User program

Startup node

Programming Device

Controller Link

+

 

 

CS/CJ-series PLCs

 

 

 

 

 

 

 

Turn ON the Start Bit in DM 30000 + 100

N.

CX-Net

(N: unit number)

 

 

 

 

 

(in CX-Programmer)

C200HX/HG/HE PLCs

 

 

 

 

 

 

 

 

 

 

Turn ON the Start Bit in AR 07

 

 

 

 

 

CVM1 and CV-series PLCs

 

 

 

 

 

Turn ON the Start Bit in DM 2000 + 100

N.

(N: unit number)

CQM1H-series PLCs

Turn ON the Start Bit in AR 07.

The data links will start when the Start Bit changes from OFF to ON or is already ON when power is turned on. The data links will stop when the Start Bit changes from ON to OFF.

Note The data in the AR and DM Areas is retained when power is turned off. There- fore, by setting in the AR and DM Areas can be made in advance to start data links as soon as power is turned on.

It is recommended to set the Start Bit to ON in multiple nodes that are partici- pating in the data link so that the data links will start even if the startup node is down. The same data link settings must be set in these nodes for automati- cally set data links.

CS/CJ-series Start Bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

Word N

N: DM 30000 + 100 (unit number)

Data link Start Bit

Start: Changed from OFF to ON or set to ON when power is turned on

Stop: Changed from ON to OFF

C200HX/HG/HE Start Bit

15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0

AR 07

Data link Start Bit for level 0 (AR 0700)

Start: Changed from OFF to ON or set to ON when power is turned on

Stop: Changed from ON to OFF

Data link Start Bit of level 1 (AR 0704)

Start: Changed from OFF to ON or set to ON when power is turned on

Stop: Changed from ON to OFF