Omron CS1W-CLK21-V1, CVM1-CLK21 Setting Routing Tables, Created, Relay Network Table, Address

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 263
Image 263

Setting Routing Tables

Section 7-4

 

2. The network address is the address of the network connected to the Unit

 

(between 1 and 127). The address is set when the local network table is

 

created.

Relay Network Table

A relay network table provides the node and network addresses correspond-

 

ing to the initial relay point (first point the data must go to) en route to a target

 

network (end network) not directly connected to the local PLC.

 

The table traces the route from the relay point to the end network.

 

The example below shows the routing tables for the route from local node

 

PLC1 (network address 1, node address 1) to PLC4 (network address 3, node

 

address 2).

 

Relay node PLC2

Relay node

Local node PLC1

PLC3

 

Node

 

Node

Node

address

3

 

address

address

 

 

1

2

Node

 

 

 

address 1

Network address 1

 

Network

 

 

 

address 2

Node address 2

Unit number 0

Destination

Node address 1 node PLC4 Unit number 1

Destination

Node address 2

Network address 3

PLC1 relay network table

End Relay Relay network network node

2 1 3

3

1

3

 

 

 

PLC2 relay network table

End Relay Relay network network node

3

2

2

 

 

 

End network

PLC3 local network table

Local

network Unit number address

2

0

 

 

3

1

 

 

Data first goes to

Data then goes to

node address 3 at

node address 2 at

network address 1 to

network address 2

reach network

to reach network

address 3.

address 3.

We know from the

Data goes to

local network table

node address 2

that the data goes

at network

through local unit

address 3, i.e.,

number 1 to reach

the local

network address 3.

network.

7-4 Setting Routing Tables

This section describes routing table settings.

Routing tables are set through the CX-Net (in CX-Programmer), SYSMAC LINK, or Controller Link Support Software. This section describes setting pro- cedures and setting details.

See the operating manual of the Programming Device you are using for the specific setting procedure.

Note 1. Routing tables cannot be set through Programming Consoles.

2.Networks cannot be crossed by a Programming Device without setting routing tables. Routing tables can therefore be set only for nodes connect- ed to the Programming Device and other nodes in the same network. Dis- connect and reconnect the Programming Device to each network when setting routing tables in multiple networks.

3.Make sure that the routing tables are properly set at all nodes on the net- work. If a message is sent to a node without correct routing tables, trans- mission will not work properly and a response may not be returned.

240