Data Link I/O Response Time

Section 8-3

CVM1 and CV-series PLCs

When a CVM1 or CV-series CPU Unit is operating in asynchronous mode,

Under Asynchronous

data exchange with the Controller Link Unit is executed as interrupt process-

Operation

ing during peripheral processing, regardless of the cycle time of PLC instruc-

 

tion execution. Data exchange timing is as follows:

 

 

PLC cycle time

 

 

 

 

 

 

 

 

Instruction execution

Execution

Execution

Execution

 

 

 

 

 

 

I/O refreshing

I/O refreshing

I/O refreshing

PLC processing

Peripheral servicing interval

 

 

 

 

 

 

 

Peripheral processing

CPU Bus

Programming

CPU Bus

Programming

CPU Bus

Programming

Device/Host Link

 

Unit service

Device/Host Link

Unit service

serviceDevice/Host Link

Unit service service

service

Basic processing

Interrupt processing

Interrupt processing

Interrupt processing

 

for data exchange

for data exchange

for data exchange

 

 

Basic processing

 

Basic processing

 

 

More than one data exchange can be executed during a PLC cycle, depend- ing on the data exchange timing. If interrupt processing for data exchange is executed, the peripheral servicing interval will be lengthened by the time required for the interrupt processing (see 8-3-2 Data Processing Time on page 254).

CS/CJ-series PLCs, CVM1

When a CS/CJ-series, CQM1H-series, CVM1, or CV-series PLC is operating

and CV-series PLCs in

in synchronous mode, a CQM1H-series, or a C200HX/HG/HE PLC is operat-

Synchronous Mode,

ing, data exchange with the Controller Link Unit is executed as processing

CQM1H-series PLCs, and

during peripheral processing for the PLC cycle. Data exchange timing is as

C200HX/HG/HE PLCs

follows:

 

PLC cycle time

PLC processing

 

Execution

I/O refreshing

Peripheral

 

service

 

 

 

 

 

 

Execution

Basic processing

Processing for

Basic processing

 

data exchange

 

If processing for data exchange is executed, the PLC cycle time will be length- ened by the time required for the interrupt processing (see 8-3-2 Data Pro- cessing Time below).

8-3-2 Data Processing Time

The time required to process data exchange (data processing time) can be roughly estimated as shown in the following table.

CPU Unit

Equation estimating data processing time

 

 

 

CS1-H, CJ1-H, CJ1M CPU Unit

0.1 ms + Number of transfer words

0.7 s

 

 

 

 

CS1, CJ1 CPU Unit

1.5 ms + Number of transfer words

1 s

 

 

 

 

CVM1-series CPU Unit

1.7 ms + Number of transfer words

1 s

 

 

 

 

The number of words processed in a single data exchange is shown in the fol- lowing table for each series of PLC. If the number of data link words exceeds the value shown in the table, data exchange will be executed as several sepa- rate processes.

254

Page 277
Image 277