Omron C200HW-CLK21, CVM1-CLK21, CS1W-RPT01, CJ1W-CLK21-V1, CQM1H-CLK21, CS1W-CLK21-V1 232

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 255
Image 255

Response Codes

 

 

Section 6-7

 

 

 

 

Main code

Sub-

Probable cause

Remedy

 

code

 

 

 

 

 

 

26: Command error

01

The specified area is not protected.

The program area is not protected, so it isn’t

 

 

This response code will be returned if

necessary to clear protection.

 

 

an attempt is made to clear protection

 

 

 

on an area that is not protected.

 

 

 

 

 

 

02

An incorrect password has been speci-

Specify a password that is registered.

 

 

fied.

 

 

 

 

 

 

04

The specified area is protected.

Execute the command again after executing

 

 

 

the PROGRAM AREA PROTECT CLEAR

 

 

 

command for the PLC.

 

 

 

 

 

 

To many commands at destination.

The destination has received more than 5

 

 

 

commands. Either interrupt servicing or wait

 

 

 

for servicing to complete before re-execut-

 

 

 

ing the command.

 

 

 

 

 

05

The service is being executed.

Execute the command again after the ser-

 

 

 

vice has been completed or aborted.

 

 

 

 

 

06

The service is not being executed.

Execute the service if necessary.

 

 

 

 

 

07

Service cannot be executed from local

Execute the service from a node that is part

 

 

node because the local node is not part

of the data links.

 

 

of the data links.

 

 

 

 

 

 

 

A buffer error has prevented returning a

Reset the board. If the error persists,

 

 

normal response.

replace the board.

 

 

 

 

 

08

Service cannot be executed because

Make the necessary settings.

 

 

necessary settings haven’t been made.

 

 

 

 

 

 

09

Service cannot be executed because

Check the command format of and make

 

 

necessary settings haven’t been made

the necessary settings.

 

 

in the command data.

 

 

 

 

 

 

0A

The specified action or transition num-

Execute the command again using an

 

 

ber has already been registered.

action or transition number that hasn’t been

 

 

 

registered.

 

 

 

 

 

0B

Cannot clear error because the cause

Eliminate the cause of the error and exe-

 

 

of the error still exists.

cute the ERROR CLEAR command.

 

 

 

 

30: Access right error

01

The access right is held by another

Execute the command again after the

 

 

node.

access right has been released.

 

 

(Either a Programming Device at the

(The command can be executed after the

 

 

other node is executing an SFC online

ACCESS RIGHT FORCED ACQUIRE or

 

 

edit, or the other node is executing an

ACCESS RIGHT RELEASE command is

 

 

ACCESS RIGHT ACQUIRE or

completed. Releasing the access right

 

 

ACCESS RIGHT FORCED ACQUIRE

might affect processes in progress at the

 

 

command.)

node that held the access right.)

 

 

 

 

40: Abort

01

Command was aborted with ABORT

---

 

 

command.

 

232

Page 255
Image 255
Omron C200HW-CLK21, CVM1-CLK21, CS1W-RPT01, CJ1W-CLK21-V1, CQM1H-CLK21, CS1W-CLK21-V1 operation manual 232