Response Codes

 

 

Section 6-7

 

 

 

 

Main code

Sub-

Probable cause

Remedy

 

code

 

 

 

 

 

 

05: Routing error

01

Destination node address is not set in

Set the destination node address in the

 

 

the routing table.

routing table.

 

 

 

 

 

02

Routing table isn’t registered.

Set the source nodes, destination nodes,

 

 

 

and relay nodes in the routing table.

 

 

 

 

 

03

Routing table error

Set the routing table correctly.

 

 

 

 

 

04

The maximum number of relay nodes

Redesign the network or reconsider the

 

 

was exceeded in the command.

routing table to reduce the number of relay

 

 

 

nodes in the command. Use a CS/CJ-series

 

 

 

CPU Unit with unit Ver. 2.0 or later with CX-

 

 

 

Programmer Ver. 4.0 or later to send com-

 

 

 

mands across three or more network levels.

 

 

 

 

10: Command format

01

The command is longer than the max.

Check the command format of the com-

error

 

permissible length.

mand and set it correctly.

 

 

 

 

 

02

The command is shorter than min. per-

Check the command format of the com-

 

 

missible length.

mand and set it correctly.

 

 

 

 

 

03

The designated number of data items

Check the number of items and the data,

 

 

differs from the actual number.

and make sure that they agree.

 

 

 

 

 

04

An incorrect command format has

Check the command format of the com-

 

 

been used.

mand and set it correctly.

 

 

 

 

 

05

An incorrect header has been used.

Set the routing table correctly.

 

 

(The local node’s relay table or relay

 

 

 

node’s local network table is wrong.)

 

 

 

 

 

11: Parameter error

01

A correct memory area code has not

Check the command’s memory area code

 

 

been used or Extended DM Area is not

and set the appropriate code.

 

 

available.

 

 

 

 

 

 

02

The access size specified in the com-

Set the correct access size for the com-

 

 

mand is wrong, or the first address is

mand.

 

 

an odd number.

 

 

 

 

 

 

03

The first address is in an inaccessible

Set a first address that is in an accessible

 

 

area.

area.

 

 

 

 

 

04

The end of specified word range

Check the acceptable limits of the data area

 

 

exceeds the acceptable range.

and set the word range within the limits.

 

 

 

 

 

 

 

Check the data link tables to be sure the

 

 

 

limit to link words has not been exceeded.

 

 

 

 

 

06

A non-existent program no. has been

Check the program number and be sure

 

 

specified.

that it is set correctly.

 

 

 

 

 

09

The sizes of data items in the com-

Check the command data and be sure that

 

 

mand block are wrong.

the sixes of the data items are correct.

 

 

 

 

 

 

 

Check the data link tables to be sure all

 

 

 

nodes in the refresh parameters are in the

 

 

 

common link parameters.

 

 

 

 

 

0A

The IOM break function cannot be exe-

Either abort the current IOM break function

 

 

cuted because it is already being exe-

processing, or wait until it is completed and

 

 

cuted.

execute the command.

 

 

 

 

 

 

 

Check the data link tables for node

 

 

 

addresses that have been set twice.

 

 

 

 

 

0B

The response block is longer than the

Check the command format and set the

 

 

max. permissible length.

number of items correctly.

 

 

 

 

 

0C

An incorrect parameter code has been

Check the command data and reenter it cor-

 

 

specified.

rectly.

 

 

 

 

 

 

 

Check the data link table file for corruption.

 

 

 

 

229

Page 252
Image 252
Omron CVM1-CLK21, CS1W-RPT01, CJ1W-CLK21-V1, C200HW-CLK21, CQM1H-CLK21, CS1W-CLK21-V1 operation manual 229