Setting Data Links

Section 5-2

 

 

 

 

Item

Setting range

 

 

 

 

Send size (number of

Set the number of words in BCD between 0 and 1,000.

 

words) for node of area 2

The total number of send words of area 1 and area 2

 

 

must not exceed 1,000.

 

 

When area 2 is not used, set to 0.

 

 

 

 

First data link status word

Set in BCD the first word used for storing data link status.

 

 

An area of 16 words is used for storing status.

 

 

0 (*) or CIO 0001 to CIO 2540

 

 

Status is stored in the CIO area only.

 

 

*: When 0 is set, the status is saved in CIO 1500 + unit

 

 

number x 25 (+ 7 to + 22).

 

 

 

 

Nodes participating in the

Set to ON (1) the bits corresponding to the nodes partici-

 

data links

pating in the data links.

 

 

The data link will not start unless the startup node itself is

 

 

set as participating node.

 

 

The data link will not start if the node is set to a parameter

 

 

exceeding the “maximum node address” of the network

 

 

parameter.

 

 

 

Note a) The total number of words in data link send and receive areas must not exceed 8,000 per node.

b)The following values must be satisfied for each node for the data link area 1 and area 2 so that the final word in the data link does not go beyond the last word in the PLC memory area.

(Data link start word – 1) + Total number of send/receive words in area 2555 (CIO Area)

199 (LR Area)

8191 (DM Area for CV500/CVM1-CPU01)

24575 (DM Area for other CPU Units)

32765 (EM Area)

c)When using area 1 only, set the data link start word, type, and the number of send words of area 2 to 0.

d)When using area 2 only, set the data link start word, type, and the number of send words of area 1 to 0.

e)The startup node must be registered as a participating node of the data links. If not, the data links will not start.

Note 1. When data links are automatically created for networks containing C200HX/HG/HE, CS/CJ-series, CVM1, CV-series, and CQM1H-series PLCs, the linkable area is restricted to the area of the C200HX/HG/HE or CQM1H-series PLC because it is smaller than that of CVM1, CV-series or CS/CJ-series PLCs.

148