System Configuration Parameters

General Information

System Configuration Parameters

The EA800 base unit requires certain system level information as outlined in Table 4.

Table 4 System Configuration Parameters

Parameter

Selections

Factory Default

 

Description

 

 

 

 

 

 

 

Date Format

• MM/DD/YYYY

MM/DD/YYYY

 

Sets the desired date format for all event time stamps.

 

 

• DD/MM/YYYY

 

 

 

 

 

 

 

 

 

 

Time Format

12-hour

24-hour

 

Sets the desired time format for all event time stamps.

 

 

24-hour

 

 

 

 

 

 

 

 

 

Data Collec-

• 30 seconds

5 minutes

Sets the interval for collecting and recording data from the

 

tion Fre-

• 1 minute

 

 

sensors. The data collection frequency applies to all sen-

 

quency

• 5 minutes

 

 

sors.The EA800 provides approximately 10,000 data

 

 

• 15 minutes

 

 

points to be collected regardless of the frequency

 

 

• 30 minutes

 

 

selected. The estimated time duration covered for each

 

 

 

 

data collection frequency is listed below.

 

 

• 60 minutes

 

 

 

 

 

 

30 seconds = 3.5 days

 

 

 

 

 

 

 

 

 

 

1 minute = 1 week

 

 

 

 

 

5 minutes = 1 month

 

 

 

 

 

15 minutes = 3 months

 

 

 

 

 

30 minutes = 6 months

 

 

 

 

 

60 minutes = 1 year

 

 

 

 

 

 

 

Buzzer

• Enable

Enabled

 

Enables and disables the buzzer when an alarm limit has

 

 

• Disable

 

 

been exceeded or a warning condition exists.

 

 

 

 

 

! WARNING

 

 

 

 

 

Selecting Disable for this parameter turns the audible

 

 

 

 

 

alarm buzzer off completely. No audible alarm tone

 

 

 

 

 

will sound when an alarm occurs if DISABLE is

 

 

 

 

 

selected.

 

 

 

 

 

 

 

RF Channel

11 (2405 MHz)

channel 16

 

Selects the ISM band radio frequency (RF) channel for

 

 

12 (2410 MHz)

 

 

transmission between the wireless sensors and EA800

 

 

13 (2415 MHz)

 

 

base unit.

 

 

 

 

 

 

 

14 (2420 MHz)

 

 

 

 

 

15 (2425 MHz)

 

 

 

 

 

16 (2430 MHz)

 

 

 

 

 

17 (2435 MHz)

 

 

 

 

 

18 (2440 MHz)

 

 

 

 

 

19 (2445 MHz)

 

 

 

 

 

20 (2450 MHz)

 

 

 

 

 

21 (2455 MHz)

 

 

 

 

 

22 (2460 MHz)

 

 

 

 

 

23 (2465 MHz)

 

 

 

 

 

24 (2470 MHz)

 

 

 

 

 

25 (2475 MHz)

 

 

 

 

 

26 (2480 MHz)

 

 

 

 

 

 

 

 

 

 