Accessories

Accessories

 

Table 14

Specifications — continued

 

 

 

 

 

 

Item

Specification

 

 

 

 

Wired Water Presence Sensor:

2-wire; maximum 304 m (1000 ft.) cabling length

 

 

 

 

Wired 4-20mA Sensor

EA800 load (160 Ohms maximum)

 

 

 

 

 

 

 

(9) Form C with 3-terminal NC/COM/NO connections.

 

Relay Outputs

Note: There are 8 primary relays (1 dedicated for each sensor) and

 

 

 

 

 

 

1 auxiliary relay.

 

 

 

 

 

Relay Contact Ratings

Max 30VDC @ 1 amp resistive.

 

Not for use with AC power.

 

 

 

 

 

 

 

Relay Logic

Each relay is user configurable.

 

 

 

 

 

Display

 

128x64 graphic LCD, with blue backlight

 

 

 

 

 

 

 

Device Environmental Operating Range:

 

 

 

 

 

Humidity:

 

5 to 95% RH, non-condensing

 

 

 

 

Temperature, Operating:

0°C to 50°C (32° F to 122° F). Not for installation inside coolers or freezers.

 

 

 

 

Ambient Environmental Quality:

Indoor use intended, non-corrosive environment

 

 

 

 

 

 

 

FCC Part 15, Subpart C, Class B

 

Conformity Certifications

ICES-003, Issue 3; 1997

 

 

 

NRTL CUE certification mark

 

 

 

 

 

Warranty

 

Two (2) Year Limited Warranty. See Warranty and Service Information.

 

 

 

 

 

Notes:

 

 

 

1. Where required, this equipment is to be isolated from the mains supply by a limited power source as specified

 

in EN60950.

 

 

2. All terminals must be connected to a Class 2 Power Limited Circuit complying with the National Electric Code

 

NFPA 70, Article 725.

 

 

3. See “Specifications” on page 46 for power supply requirements.

 

 

 

 

Accessories

Accessories available for use with the EA800 Environmental Alarm System are listed below.

Table 15

Accessories

 

 

 

Item (Winland Part Number)

Description

 

 

BZ-3: Audible alarm module

Buzzer for connection to auxiliary relay output that provides audible alarm

(PN 1183)

 

indication.

 

 

 

 

 

Regulated 110 VAC-to-12 VDC @ >500 mA (minimum) transformer suitable for

Power supply (transformer)

use with EA800.

 

(PN L-020-0085)

Note: Power supply must be a limited power source per notes 1 and 2 in

 

 

 

 

Table 14.

 

 

 