Connecting Wired HA-III+ Humidity Sensors

Installation

Connecting Wired HA-III+ Humidity Sensors

1.Make certain the sensor's wiring is passed through the opening in the mounting plate.

2.Remove the adapter from the correct input connector headers by pulling the adapter up and off of the circuit board header connectors.

3.Strip the ends of each of the sensor's wires as indicated by the gauge on adapter you just removed.

4.Insert the stripped wire ends into screw terminals of the adapter as indicated by your EA800 Wiring Diagram you completed in the preparation phase. Observe proper polarity. See Figure 15.

Base Unit-Powered

External Adapter-Powered

EA800 Base Unit

 

J5

 

J6

 

Aux Power Out

 

Input N

 

 

NC

 

User

 

 

 

supplied

 

 

 

cable

 

NC

 

PowerInput

HAGND

SOURCE

-III+

 

 

SINK

 

 

Connector

 

 

EA800 Base Unit

 

External

J5

 

J6

 

Power

 

 

Aux Power Out

 

Input N

Adapter

 

 

 

 

 

 

 

 

NC

 

 

User

 

 

 

 

supplied

 

 

 

 

cable

 

NC

 

 

 

 

 

 

PowerInput

GND

SINK

SOURCE

 

 

HA-III+

 

 

 

Connector

 

Figure 15 EA800 Base Unit Wired HA-III+ Sensor Connections

5.Secure the connections using the setscrews on the adapter. Check the connection by lightly pulling on each connection.

6.After connecting the wire ends to the adapter, align the adapter to the correct header pins as indicated by your EA800 Wiring Diagram, and press the adapter fully onto the header connector pins.