Enviro EA800 owner manual Editing Sensor Parameters, SENSORS screen

Models: EA800

1 98
Download 98 pages 50.46 Kb
Page 62
Image 62
SENSORS screen:

Editing Sensor Parameters

5.If the detected new sensor is not the same type as the replaced sensor, the INVALID SENSOR TYPE screen is displayed. Press OK (F3) to return to the

SENSORS screen:

6.Do one of the following:

Replace the physical sensor with one that matches the type of the replaced sensor and repeat this procedure.

Delete the sensor from the base unit and replace with the new sensor (of a different type). See “Deleting a Sensor” on page 59 and “Adding a Sensor” on page 57.

7.If you wish to replace another wireless sensor, repeat this procedure.

8.If you are finished performing sensor maintenance, press Editing Sensor ParametersManual background to exit maintenance and resume monitoring.

9.Press F1 to lock the keypad.

Editing Sensor Parameters

The general procedure for editing sensor parameters is provided below. Not all sensor parameters can be edited for an installed sensor. The editable parameters are dependent on the installed sensor, so the EDIT SENSOR screen varies according to the sensor selected. You cannot edit the following:

The low and high scaled values for a 4-20mA sensor. If these require changes, you must delete the 4-20mA sensor and re-add it to the system. See “Connecting Wired HA-III+ Humidity Sensors” on page 25.

A sensor’s type. For example, if a 4-20mA sensor was incorrectly added as a Blue temperature sensor, you must delete the incorrect sensor and then re-add the correct sensor.

The unit of measure. If unit of measure must be changed, the sensor must be deleted and re-added to the system.

Note: Update the system’s Configuration Worksheets to document changes.

Unlock the EA800 as shown in “Locking and Unlocking the EA800” on page 55

Select the parameter to be edited.

Select the sensor to edit.

Use PREV, NEXT, and arrow keys to change value as required.

F3

To edit another parameter

when done editing

F1 to lock

58

D-011-0152

Page 62
Image 62
Enviro EA800 owner manual Editing Sensor Parameters, SENSORS screen