Connecting the EA800 Alarm Outputs

 

 

If the EA800 base unit will be connected to a remote alarm panel, do not connect

!

CAUTION

the base unit to the alarm panel until after sensor connection and configuration

 

 

 

 

is complete. Connecting the remote alarm panel before configuring the EA800

 

 

sensors will result in false alarms at the remote panel.

1.If alarm loops will be controlled by the EA800, install all required wiring from alarm loops to the EA800 mounting location.

2.Connect the alarm loop leads to the terminal block adapter. Attach the adapter to terminals C and either NC or NO on the appropriate circuit board header connector.

3.Repeat the previous step for each alarm loop.

4.Engage the mating tabs on the EA800 main chassis into the mounting plate upper hinges.

5.Pivot the bottom of the EA800 main chassis into closed position while aligning the retainer tabs on the main chassis with the holes in the rear mounting plate and ensure that the wiring is not pinched, stressed, or protruding between the chassis halves.

6.Snap the main chassis closed onto the mounting plate. When properly closed, the main chassis and mounting plate mating surfaces are flush.

Programming

When powered-up, the EA800 is ready for programming. The following is an overview of the general process for programming the EA800:

View the MAIN MENU and unlock the EA800 as described in “Accessing the MAIN MENU for Programming” on page 28.

Set the system configuration as described in “Configuring System Parameter Settings” on page 28.

Set the current date as described in “Setting the Current Date” on page 31.

Set the current time as described in “Setting the Time” on page 32.

Add the wireless sensors. See the appropriate subsection under “Adding Wireless Sensors” on page 33.

Add the wired sensors. See the appropriate subsection under “Adding Wired Sensors” on page 43.

Verify performance of the wireless sensors. See “Verify Wireless Signal Strength” on page 42.

Configure the relays. See “Configuring the Relays” on page 48.

 

 

If the EA800 base unit will be connected to a remote alarm panel, do not connect

!

CAUTION

the base unit to the alarm panel until after sensor connection and configuration

 

 

 

 

is complete. Connecting the remote alarm panel before configuring the EA800

 

 

sensors will result in false alarms at the remote panel.

Note: When no sensors are programmed in the EA800 system, the EA800 base unit boots up with a 30-minute delay before the alarm buzzer sounds. At this time the Alarm screen is displayed with a System Alarm caused by the fact that no sensors have been programmed yet. To prevent the System Alarm from going off, you must program at least 1 connected sensor into the EA800 base unit prior to the end of the