Relay Operation

 

 

 

 

General Information

 

 

 

 

 

 

Table 11

Sensor Parameter Descriptions — continued

 

 

 

 

 

Parameter

Applicable to Sensors

Description

 

 

 

 

 

High Alarm

• Blue, Red and White

The High Alarm Limit sets the value that trips the high alarm when

 

Limit

 

temperature sensors

exceeded.

 

 

 

HA-III+

 

 

 

 

4-20mA sensor

 

 

 

 

• Wireless humidity

 

 

 

 

sensor

 

 

 

 

• Wireless

 

 

 

 

temperature sensor

 

 

 

 

 

 

Alarm Delay

All

This sets the time period that an alarm condition can exist before the

 

Time

 

 

alarm is triggered. This is useful for helping to prevent false alarms from

 

 

 

 

occurring in situations where normal activities cause conditions to tem-

 

 

 

 

porarily exceed alarm thresholds. For example, the temperature in a

 

 

 

 

freezer may temporarily rise above the High alarm limit while frozen food

 

 

 

 

is being restocked and the freezer door is open, but the delay prevents

 

 

 

 

the alarm from going off unless the temperature fails to cool below the

 

 

 

 

alarm threshold within the alarm delay period.

 

 

 

 

 

Relay Operation

This section describes the operation of the base unit's relays. The relays must be programmed correctly so that their outputs provide the desired signaling to the alarm panel.

Table 12 Relay Configuration Settings

Relay Setting

Description

No Alarm

No Alarm: Power is removed from the relay coil as shown below.

Relay State:

 

 

 

 

To

De-Energized (default)

 

 

 

NC

 

 

 

alarm

 

 

C

panel

 

 

 

 

NO

 

 

 

Idc = 0

From

EA800

logic Manual background

Alarm: Power is applied to the relay coil as shown below.

NC

To

alarm

C

panel

NO

Idc

 

From

 

EA800

 

logic

 

No Alarm

No Alarm: Power is applied to the relay coil as shown below.

Relay State: Energized

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To

 

 

 

 

 

 

 

 

 

 

 

 

 

NC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

alarm

 

 

 

 

 

C

 

 

 

 

 

 

 

panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

From

Idc

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EA800

 

 

 

 

 

 

 

 

 

logic

 

 

 

 

 

 

 

 

 

 

 

Alarm: Power is removed from the relay coil as shown below. This provides for a

 

default alarm if the EA800 loses power in addition to the sensors' alarms.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC

 

 

 

 

 

 

C

 

 

 

 

alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

panel

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

 

From

 

Idc = 0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EA800

 

 

 

 

 

 

 

logic

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Active Condition:

Sets the alarm to be active when an alarm condition exists.

Alarm Only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Active Condition:

Sets the alarm to be active when an alarm condition exists or a warning is active.

Alarm or Warning (default)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 