Omron CS1W-RPT01, CVM1-CLK21 Connecting the Communications Cables, Using a Relay Terminal Block

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 91
Image 91

Wiring

Section 3-3

Using a Relay Terminal Block

 

 

 

CVM1-CLK21

 

CS1W-CLK21-V1

 

 

 

 

 

 

CJ1W-CLK21-V1

C200HW-CLK21

Relay

Terminating

 

 

(End node)

 

Terminating

 

(End node)

Terminal

resistance

TER SW

resistance

TER SW

 

Block (see

(OFF)

ON

 

(ON)

ON

 

 

 

 

 

note 1.)

 

 

 

 

BD

H

BD H

 

 

BD H

 

 

 

 

 

 

 

 

BD L

 

 

BD L

 

 

BD

L

SHLD

TER

SHLD

SHLD

SW

Terminating resistance

(ON) ON

Ground

Note 1. Mounting and dismounting during communications is not possible for Re- lay Terminal Blocks connected to the nodes at the ends of the network (i.e.: the nodes with terminating resistance).

2.Use the recommended crimp terminals when connecting the cable’s signal lines or shield line to the terminal blocks. Short circuits can damage the Units.

Connecting the Communications Cables

Use crimp terminals when connecting communications cables to a Controller Link Unit. Use the following procedure to connect communications cables to a terminal block.

1,2,3... 1. Peel back the cover of the cable for about 50 mm without scratching the mesh of the shield. Do not peel too much because it may cause a short- circuit.

Approx. 50 mm

2.Twist the mesh of the shield to form a line.

3.Leave the tip of the wire created by twisting the shield exposed and cover the remaining section with a heat-shrinking tube.

Wire created by twisting the shield

Cover with a heat-shrinking tube

Exposed portion for crimp terminal connection

4.Remove enough of the cover from the signal lines to allow the crimp termi- nals to be connected, taking care not to damage the signal lines. Damage to the signal lines could cause the cable to break.

68

Page 91
Image 91
Omron CS1W-RPT01, CVM1-CLK21, CJ1W-CLK21-V1, C200HW-CLK21 Connecting the Communications Cables, Using a Relay Terminal Block