Omron CVM1-CLK21, CS1W-RPT01, CJ1W-CLK21-V1, C200HW-CLK21, CQM1H-CLK21, CS1W-CLK21-V1 319

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 342
Image 342

Error Log

 

 

 

 

Section 9-3

 

 

 

 

 

 

 

 

Error

Contents

Detail code

Correction

Written to

 

Applicable

code

 

 

 

 

EEPROM

 

PLC

 

1st byte

2nd byte

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0216

Backup power supply error (Opti-

00 Hex

Backup

Check the status of

No

 

CS/CJ

Hex

cal Units only)

 

power sup-

the backup power

 

 

 

 

 

 

ply error dis-

supply and power

 

 

 

 

 

 

tinction:

supply cables.

 

 

 

 

 

 

01 Hex:

 

 

 

 

 

 

 

OFF to ON

 

 

 

 

 

 

 

02 Hex: ON

 

 

 

 

 

 

 

to OFF

 

 

 

 

 

 

 

 

 

 

 

 

021A

Set table logic error

00 Hex

01 Hex: Net-

Remake and set the

Yes

 

All

Hex

 

 

work param-

appropriate data.

 

 

 

 

 

 

eters

Check the unit ver-

 

 

 

 

 

 

02 Hex:

 

 

 

 

 

 

sion.

 

 

 

 

 

 

Data link

 

 

 

 

 

 

 

 

 

 

 

 

 

tables

 

 

 

 

 

 

 

03 Hex:

 

 

 

 

 

 

 

Routing

 

 

 

 

 

 

 

tables

 

 

 

 

 

 

 

 

 

 

 

 

021B

Hardware error

00 Hex

Error status

Replace the Control-

No

 

All

Hex

 

 

(See note.)

ler Link Unit.

 

 

 

 

 

 

 

 

 

 

 

021C

Data link error inactive

Not set

 

Restart the Control-

Yes

 

All

Hex

 

 

 

ler Link Unit.

 

 

 

 

 

 

 

 

 

 

0220

Reduced number of participating

Separated nodes 1 to 16

Check the node

No

 

CS/CJ

Hex

nodes (separated nodes)

correspond to bits 0 to 15

parameters, the sep-

 

 

 

 

 

(1st byte: bits 8 to 15, 2nd

arated nodes,

 

 

 

 

 

byte: bits 0 to 7)

cables, and terminat-

 

 

 

 

 

 

 

ing resistance set-

 

 

 

0221

 

Separated nodes 17 to 32

 

 

 

 

tings.

 

 

 

Hex

 

correspond to bits 0 to 15

 

 

 

 

 

 

 

 

 

 

(1st byte: bits 8 to 15, 2nd

 

 

 

 

 

 

byte: bits 0 to 7)

 

 

 

 

 

 

 

 

 

 

 

0222

 

Separated nodes 33 to 48

 

 

 

 

Hex

 

correspond to bits 0 to 15

 

 

 

 

 

 

(1st byte: bits 8 to 15, 2nd

 

 

 

 

 

 

byte: bits 0 to 7)

 

 

 

 

 

 

 

 

 

 

 

0223

 

Separated nodes 49 to 62

 

 

 

 

Hex

 

correspond to bits 0 to 13

 

 

 

 

 

 

(1st byte: bits 8 to 15, 2nd

 

 

 

 

 

 

byte: bits 0 to 7)

 

 

 

 

 

 

 

 

 

 

 

 

0230

Data link stop requested

Start node

Stop node

Check the applica-

Yes

 

CS/CJ

Hex

 

address

address

tion and Support

 

 

 

 

 

 

 

Software operation if

 

 

 

 

 

 

 

the data link was not

 

 

 

 

 

 

 

intentionally stopped.

 

 

 

 

 

 

 

 

 

 

 

0300

Packet discarded

Not set

 

Conduct an echo-

No

 

All

Hex

 

 

 

back test and find the

 

 

 

 

 

 

 

cause of the error.

 

 

 

 

 

 

 

 

 

 

 

0601

Unit error

Not set

 

Check the operating

Yes

 

All

Hex

 

 

 

environment.

 

 

 

 

 

 

 

 

 

 

 

Note 1. Applicable PLCs: CV = CVM1 and CV-series PLCs, CS/CJ = CS-series and CJ-series PLCs, All = All models of PLC.

2.Errors indicated by error codes 0101 to 0116 are recorded only when the frame was discarded because transmission was impossible.

3.Error code 0230 hex is only recorded for Controller Link Units with unit ver- sion 1.2 or later.

319

Page 342
Image 342