Status Area and Troubleshooting

 

Section 9-2

 

 

 

 

 

Bit status

Probable cause

Probable remedy

 

 

 

 

 

Receive area insufficient

The send area at the rele-

When the intention is not to

 

(short) is 1: ON

vant node is larger than the

receive all data, use as is

 

 

receive area and some

(data that cannot be

 

 

data cannot be received.

received will be read and

 

 

 

discarded.)

 

 

 

When it differs from the

 

 

 

intended data link, check

 

 

 

the number of send words

 

 

 

at the relevant node, the

 

 

 

number of receive words at

 

 

 

the local node and the off-

 

 

 

set, then reset the data link

 

 

 

table correctly.

 

 

 

 

 

Receive area remaining is

The send area at the rele-

When the intention is to

 

1: ON

vant node is smaller than

leave some space in the

 

 

the receive area and some

receive area, use as is (the

 

 

of the area will be unused.

surplus receive area will be

 

 

 

cleared to 0.)

 

 

 

When it differs from the

 

 

 

intended data link, check

 

 

 

the number of send words

 

 

 

at the relevant node, the

 

 

 

number of receive words at

 

 

 

the local node and the off-

 

 

 

set, then reset the data link

 

 

 

table correctly.

 

 

 

 

Other Status

 

 

 

 

 

 

 

Bit status

Probable cause

Probable remedy

 

 

 

 

 

Error log exists (IR 19015)

Error information on the

Using the Controller Link

 

is 1: ON

Controller Link Unit (an

Support Software or an

 

 

error log) has been

FINS command, read the

 

 

recorded.

cause of the current error.

 

 

 

Alternatively, use past error

 

 

 

log records to troubleshoot

 

 

 

the problem.

 

 

 

 

 

Communications controller

The Controller Link Unit is

Replace the Controller Link

 

send error (IR 19011) is 1:

faulty.

Unit.

 

ON

 

 

 

 

 

 

 

Inconsistent network

Indicates that the network

Check the network param-

 

parameters (IR 19010) is 1:

parameters recorded in the

eters on the Network in

 

ON

CPU Unit’s EEPROM differ

use using the Controller

 

 

from the values of the Net-

Link Support Software, and

 

 

work in use.

reset necessary parame-

 

 

 

ters.

 

 

 

 

 

Node address duplicate

The same node address

Reset so that each node

 

setting error (IR 19009) is

has been used more than

address is used only once

 

1: ON

once.

within the same Network.

 

 

 

 

 

EEPROM error (IR 19007)

An error has occurred

Check the status of bits

 

is 1: ON

while writing data to the

IR 19000 to IR 19002 and

 

 

CPU Unit’s EEPROM.

correct any problems

 

 

 

found. If the error occurs

 

 

 

again, replace the CPU

 

 

 

Unit.