Data Link I/O Response Time

 

 

 

Section 8-3

 

The number of bytes in each message differs according to the instruction

 

being issued.

 

 

 

 

 

 

 

 

 

 

 

 

 

Instruction

When sent

 

 

When received

 

 

 

 

 

 

 

 

SEND

Number of words to be sent 2

 

14

 

 

 

+ 18

 

 

 

 

 

 

 

 

 

 

 

 

RECV

18

 

 

Number of words to be

 

 

 

 

 

 

received 2 + 14

 

 

 

 

 

 

 

 

CMND

Number of bytes in command

 

Number of bytes in response

 

 

 

data + 10

 

 

data

 

Calculation Example

 

 

 

 

 

Communications conditions are as follows:

 

 

 

Transmission medium:

Twisted-pair cables

 

Baud rate:

 

2 Mbps

 

 

 

Network parameters:

Defaults

 

Max node address:

32

 

 

 

 

Polled nodes per comm cycle:

4

 

 

 

 

Event-frames per comm cycle:

35

 

 

 

 

Network configuration:

8 nodes

 

Nodes that send messages:

2 nodes

 

Bytes in all messages sent:

2,012

2 bytes

In this example, B to E in the equation have the following values.

B:4

C:8

D:2

E:4,024

The communications cycle time is thus as follows:

600 4 + 110 8 + 320 2 + 4 4,024 + 2,290 = 22,306 (s)

22 (ms)

8-3 Data Link I/O Response Time

When accurate communications timing is required, you need to understand data exchange timing and the time required for data transmission and recep- tion via data links. Use the information described in this section as reference information for system construction.

8-3-1 Data Exchange Timing

This section describes data exchange timing for data links between the Con- troller Link Unit and the PLC’s CPU Unit. Data exchange is executed as inter- rupt processing during CPU Bus Unit or Programming Device/Host Link servicing performed by the CPU Unit. This interrupt processing is executed each time data exchange between the local node and each node connected via a data link is completed.

Data exchange timing differs depending on the CPU Unit model and the CPU

Unit the Execute Process (asynchronous or synchronous) specified in PLC

Setup, as described below.