Omron C200HW-CLK21 Features and Functions of Version-1 Models, Devices can be modularized

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 33
Image 33

Overview

Section 1-1

If Repeater Units are installed at likely future branch points in the network in advance, new nodes can be added by simply connecting them to these Repeater Units.

The total length of wired networks can be extended.

At a baud rate of 2 Mbps, conventional wired networks can be up to 500 m long. By using two Repeater Units, this can be extended to a maximum of 1.5 km.

The maximum number of nodes can be extended to 62 for wired networks.

By combining version-1 Controller Link Units/Support Boards and a Repeater

Unit, it is possible to construct networks containing up to 62 nodes.

Improved noise resistance through the use of optical cabling.

By installing two Wire-to-Optical Repeater Units, optical cabling can be used for sections of the network that are the source of noise.

Devices can be modularized.

Devices can be modularized according to Repeater Units, making wiring easier when adding, removing, or modifying devices.

When starting up devices, components can be added to the network and debugged as they are completed.

Features and Functions of Version-1 Models

The following features and functions apply to the CS1W-CLK21-V1 and

CJ1W-CLK21-V1 Controller Link Units and the 3G8F7-CLK21-V1 Controller

Link Support Board only.

Up to 62 nodes can be connected.

Overview

When a CS1W-RPT01 Repeater Unit is used, the maximum number of nodes that can be used in the network increases to 62. (The previous limit was 32.)

Method

Use Repeater Units and turn ON bit 11 (Wired Network 62 Node Enable Bit) in the DM Parameter Area software switch D30000 + 100 Unit No. of all nodes to enable a maximum of 62 nodes.

Restrictions

The maximum 62 nodes cannot be achieved if version-1 models and pre-ver- sion-1 models are used together in the same network.

Automatic data link creation is possible with 1:N allocations.

Overview

It is possible to perform unequal 1:N allocations of data between nodes with automatic data link creation. This makes it easy to perform data links that for- merly required the user to manually edit data link parameters.

The following four automatic data link creation patterns can be used:

Equality layout (the previous pattern)

1:N allocation, common type

1:N allocation, 1 to 1 type

1:N allocation, chain type

10

Page 33
Image 33
Omron C200HW-CLK21, CVM1-CLK21 Features and Functions of Version-1 Models, Total length of wired networks can be extended