Omron CJ1W-CLK21-V1, CVM1-CLK21, CS1W-RPT01 DM Area CS/CJ CPU Bus Unit Area, Unit no Words

Models: CS1W-RPT01 CJ1W-CLK21-V1 CVM1-CLK21 CQM1H-CLK21 CS1W-CLK21-V1 C200HW-CLK21

1 401
Download 401 pages 33.98 Kb
Page 374
Image 374

Memory Areas

Appendix B

DM Area: CS/CJ CPU Bus Unit Area

The CS/CJ CPU Bus Unit Area (DM Area) is allocated to CS/CJ CPU Bus Units according to the unit numbers assigned to them, as shown below. Each Unit is allocated 100 words, of which 10 words are used. In the Con- troller Link Unit this area is called the DM Area.

Unit no.

Words

 

Unit no.

Words

 

 

 

 

 

0

DM30000 to

8

 

DM30800 to

 

DM30009

 

 

DM30809

 

 

 

 

 

1

DM30100 to

9

 

DM30900 to

 

DM30109

 

 

DM30909

 

 

 

 

 

2

DM30200 to

10

 

DM31000 to

 

DM30209

 

 

DM31009

 

 

 

 

 

3

DM30300 to

11

 

DM31100 to

 

DM30309

 

 

DM31109

 

 

 

 

 

4

DM30400 to

12

 

DM31200 to

 

DM30409

 

 

DM31209

 

 

 

 

 

5

DM30500 to

13

 

DM31300 to

 

DM30509

 

 

DM31309

 

 

 

 

 

6

DM30600 to

14

 

DM31400 to

 

DM30609

 

 

DM31409

 

 

 

 

 

7

DM30700 to

15

 

DM31500 to

 

DM30709

 

 

DM31509

 

 

 

 

 

Software Switches (DM30000 + 100 Unit No.) (See pages 145, 243, 249, 318.)

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

 

0

 

 

 

 

0

0

 

 

0

 

0

0

 

 

 

 

 

 

 

 

 

0

0

0

 

 

 

0: Always set to 0.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data Link Start Bit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Data link status

 

 

 

 

Data link mode

 

 

 

Start: Changed from OFF to ON or set to ON

 

 

 

 

 

 

 

storage format

 

 

 

 

 

 

 

when power is turned ON.

 

 

 

 

 

 

 

 

 

 

 

000: Manual

 

 

 

 

 

 

 

 

 

 

0: 8-bit format

 

 

 

 

001: Automatic, equality layout Stop: Changed from ON to OFF.

 

 

 

 

 

 

 

1: 4-bit format

 

 

 

 

101: Automatic, 1:N allocation

Wired Network 62 Node

Enable Bit

0:32 nodes max.

1:62 nodes max.

CS1 CPU Bus Unit PLC Setup Initialization (See note 1.)

0:Do not initialize CS1 CPU Bus Unit PLC Setup

1:Initialize CS1 CPU Bus Unit PLC Setup

Polling node/polled node bit

0:Polling node

1:Polled node

Note 1: Initializes the network parameters registered in the CS1 CPU Bus Unit PLC Setup Area on the CPU Unit and clears the data link tables.

2:Be sure to set the bit in the DM Area's (CPU Bus Unit Area's) software switches (D30000 + 100unit number) described as "always set to 0" to 0. Not doing so may result in the data link not starting properly. If a data link is started with bit 7 of the software switches set to 1, the data link status will be stored in a format different to the one described in this manual (when using CS-series or CJ-series Controller Link Units).

351