Troubleshooting Using Indicators

 

Section 9-1

 

 

 

 

 

Problem

Status

Cause and remedy

 

 

 

 

 

The data link status

The data link status

The default area for storing data link

 

is showing statuses

storage area is set to

status is the Special I/O Unit Area. The

 

of 32 nodes only.

default settings, and

data for only node addresses 1 to 32 is

 

 

the data link status

reflected when the data link status stor-

 

 

storage format speci-

age format specification is set to 8 bits.

 

 

fication in the DM

 

 

 

Parameters Area is

 

 

 

set to the 8-bit for-

 

 

 

mat.

 

 

 

 

 

 

 

The polling node is a

The Units that can be used to configure

 

 

C200HW-CLK21,

a network of a network that uses a

 

 

CQM1H-CLK21,

node address higher than 32 are the

 

 

CVM1-CLK21,

CS1W-CLK21-V1 and CJ1W-CLK21-

 

 

CS1W-CLK21, or

V1 only. Either configure the network

 

 

CJ1W-CLK21.

using compatible Units and Boards, or

 

 

 

split the network into two separate net-

 

 

 

works.

 

 

 

 

 

 

The polling node is a

The Wired Network 62 Node Enable Bit

 

 

CS1W-CLK21-V1 or

in the DM Parameters Area of the poll-

 

 

CJ1W-CLK-V1.

ing node (CS1W-CLK21-V1 or CJ1W-

 

 

 

CLK-V1 with INS indicator ON) is OFF.

 

 

 

Turn ON the Wired Network 62 Node

 

 

 

Enable Bit, then turn the power supply

 

 

 

OFF and ON again.

 

 

 

 

 

Error occurs when

The data link table

The Units that can be used to configure

 

transferring data link

being transferred is

a network of a network that uses a

 

tables.

for a C200HW-

node address higher than 32 are the

 

 

CLK21, CQM1H-

CS1W-CLK21-V1 and CJ1W-CLK21-

 

 

CLK21, CVM1-

V1 only. Either configure the network

 

 

CLK21, CS1W-

using compatible Units and Boards, or

 

 

CLK21, or CJ1W-

split the network into two separate net-

 

 

CLK21.

works.

 

 

 

 

 

The data link status

The polling node is a

 

 

is showing statuses

C200HW-CLK21,

 

 

of 32 nodes only.

CQM1H-CLK21,

 

 

 

CVM1-CLK21,

 

 

 

CS1W-CLK21, or

 

 

 

CJ1W-CLK21.

 

 

 

 

 

 

 

The polling node is a

The Wired Network 62 Node Enable Bit

 

 

CS1W-CLK21-V1 or

in the DM Parameters Area of the poll-

 

 

CJ1W-CLK-V1.

ing node (CS1W-CLK21-V1 or CJ1W-

 

 

 

CLK-V1 with INS indicator ON) is OFF.

 

 

 

Turn ON the Wired Network 62 Node

 

 

 

Enable Bit, then turn the power supply

 

 

 

OFF and ON again.

 

 

 

 

282

Page 305
Image 305
Omron CS1W-CLK21-V1, CVM1-CLK21, CS1W-RPT01, CJ1W-CLK21-V1, C200HW-CLK21, CQM1H-CLK21 operation manual 282